animeo
LON 4 DC/E MOTOR CONTROLLER. REF. 5126138 B -
6/16
Anschluss an …
Forbindelse til …
Connection to …
Leitung
Kabel
Cable
Verdrilltes Adernpaar
Parsnoet
Twisted Pair
Max. Länge
Maks. længde
Max. length
Motors
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
2
/14 AWG
–
20 m/66 ft
Switches
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
2
/14 AWG
Recommended
100 m/330 ft
Group control
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 1.5 mm
2
/16 AWG
Recommended
50 m/165 ft
LON bus
2 x 0.8 mm/20 AWG
Required, following LON topology guidelines,
www.lonmark.org
-
220-230 V C
Min.: 2 x 1.5 mm
2
/16 AWG
Max.: 2 x 2.5 mm
2
/14 AWG
–
VERDRAHTUNG KABELING WIRING
Further information can be found on
www.somfyarchitecture.com
A
PICTURES
[1]
LON 4 DC/E Motor Controller WM 220-230 V AC,
wall-mounted version
[2]
LON 4 DC/E Motor Controller DRM 220-230 V AC,
DIN-rail version
B
MOUNTING
[1]
Choose the optimal location: flat and large surface
or electric cabinet. Close door!
[2]
Needed space for the DIN-rail version
1.
Mounted in an electrical cabinet
[3]
Mounting of the LON 4 DC/E Motor Controller
[4]
Use cable tie
[5]
Keep to minimum distance
C
WIRING
[1]
Tool for all terminals
[2]
Wiring diagram LON 4 DC/E Motor Controller
D
COMMISSIONING
[1]
Check the correct running direction of the end pro-
ducts (group and local control inputs)
UP: end products move upwards (C +
▲
)
STOP: end products stop (C +
▼
+
▲
)
DOWN: end products move downwards (C +
▼
)
H
To close window press UP,
to open window press DOWN
Correct the wiring if the running directions are incorrect.
[2] Push buttons
1.
Smoove IB, ref. 1811272
2.
Double push button unlocked
[3]
Attach the Motor Controller address label in ac-
cordance with the motor output in a plan or a list
[4]
Reset / Prog button: Factory reset of the LON Motor
Controller.
E
CONFIGURATION/ERROR MONITORING
[1] Mode selection DC or DCE
H
Default mode is DCE!
Type of motors which can be controlled are DC or
DCE (when a LW25-E83 motor is used; it is identifi-
able with 3 wires).
1.
To toggle between modes, give a short press
on the Reset/Prog button. Repeat this until the
desired LED lights up.
H
Using an unauthorised functional mode can
damage the motors! The mode can be specified
only for all 4 motor outputs.
[2]
Error monitoring
H
1.
LED flashes red:
short circuit/interruption motor cable
LED flashes yellow:
motor speed can not be reached
2.
LED’s show the concerned motor output
EN
H
If you do not use Somfy motors please follow
the additional information in our detailed
installation guide (www.somfy.com).