Weather Station KNX
■
Mount enclosed guide blade (11) in the fields provided next to the connection (7).
If mounted on a mast without the guide blade, no correct wind direction measurement is
possible due to the resulting turbulences.
■
Route the power supply line through the mast.
■
Attach the 7-pin plug to the connection (7). Tighten threaded ring with max. 0.5 Nm.
■
Mount weather station onto the mast and align. The grub screw (2) must be pointing
north.
■
Tighten grub screw (2) with max. 0.6 Nm.
Mounting weather station with fastening arm on mast or wall
Figure 7: Mounting with fastening arm
Mount enclosed fastening arm onto a suitable mast or wall.
The enclosed hose clamps are suitable up to a maximum mast diameter of 60 mm.
If mounted on the supplied fastening arm, do not mount the enclosed guide blade.
■
Mast mounting: Attach fastening arm to mounting mast using the enclosed hose clamps.
■
Wall mounting: Attach fastening arm to the wall through the boreholes (Figure 8) using
suitable screws.
■
Route the power supply line along the underside of the fastening arm and guide the 7-pin
plug through the open pipe socket at the end of the fastening arm.
■
Attach the 7-pin plug to the connection (7). Tighten threaded ring with max. 0.5 Nm.
■
Mount weather station onto the mast and align. The grub screw must be pointing north.
■
Tighten grub screw with max. 0.6 Nm.
■
Route the power supply line through the cable bushing into an installation pipe.
Figure 8: Fastening arm – dimensions for boreholes
Mounting and connecting the device
■
Connect bus line and external power supply to power supply line.
red
KNX+
4 / 8
82590128
16.02.2021
5158881A