background image

1. Press and 

HOLD NO

, then

2. Press and 

HOLD WEEK DAY

 until 

SET POINT 

TEMPERATURE

 displays 

FP

 (Filter Period). The clock 

display will begin fl ashing 

01

 (1 Month).

3. Press 

UP

 or 

DOWN

 to change fi lter months

4. Press 

RUN

 to advance to 

SP

 (Service Period). The clock 

display will begin fl ashing 06 (6 months)

5. Press 

UP

 or 

DOWN

 to change service months.

6. Press 

RUN

 to advance to 

ULP

 (UV Light Period). The clock 

display will begin fl ashing 00 (0 or zero months)

7. Press 

UP

 to set UV Light months.

8. Press 

RUN

 to fi nish

Tip:

  Count number of months to next Filter Check, 

System Service CFS or UV Light CFS and enter that 
number.

Adjusting Filter, Service

and UV Light Period (Months)

10

FH 04 00

Содержание VT1007

Страница 1: ...Talking Thermostat Key Information Guide Models VT1007 VT2007 VT2207...

Страница 2: ......

Страница 3: ...lay 13 Clearing CFS UV Light Display 13 Resetting Filter Months or Hours CFS Svc CFS UVL CHK FILT 13 Turning Off CHK FILT Alert 9 Heat Pump Activating Emergency Heat Eon 6 14 Reducing 2nd Stage Time D...

Страница 4: ...Call For Service Press REPORT ALERT LIGHT When Flashing Press REPORT Key to hear alert message To Raise Temperature Press UP To Lower Temperature Press DOWN FUNCTION Key Press BRIEFLY to backlight di...

Страница 5: ...TEMPERATURE starts to FLASH RELEASE Press the UP or DOWN key to raise or lower INDOOR TEMPERATURE to the desired setting When finished press RUN NOTE Indoor Temperature calibration is limited to 3 F...

Страница 6: ...ther and HOLD until INDOOR TEMPERATURE starts to FLASH RELEASE Press BOTH again until Cr1 appears in setpoint location Press UP and DOWN key to move to the desired setting Press Run Cr1 will appear he...

Страница 7: ...Escape Program Mode If during programming you get lost or wish to quit press RESET You will exit the programming mode without making changes 2 FFr Escapes Faulty Operation Static discharge can cause f...

Страница 8: ...FF and back ON in less than 5 minutes the unit will activate the time delay COOL and DELAY will FLASH Press the NO and FUNCTION keys and HOLD for 8 seconds This will disable the time delay feature for...

Страница 9: ...tructions to change the time and day of the week RUN KEY Press to advance to next step when programming NOTE On heat pump models pressing and holding RUN and YES will send thermostat into emergency or...

Страница 10: ...on Press Full lock out prevents unauthorized users from making changes Press and hold YES and HELP keys until you hear OFF and hold NO and ON OFF keys for 6 seconds Audio plays OFF when any program bu...

Страница 11: ...Setpoint Temperature 8 Press and HOLD the UP key for 8 seconds to activate the VOICE ON when changing setpoint temperature Press and HOLD the DOWN key for 8 seconds to activate the VOICE OFF when cha...

Страница 12: ...O 24 MONTHS ULP UV Light Period Range 0 TO 24 MONTHS Optional Default Hours Settings FILTER HOURS 400 HOURS after 400 hours CHK FLT appears SERVICE HOURS 3000 HOURS after 3000 hours CFS appears UV LIG...

Страница 13: ...e Period The clock display will begin flashing 06 6 months 5 Press UP or DOWN to change service months 6 Press RUN to advance to ULP UV Light Period The clock display will begin flashing 00 0 or zero...

Страница 14: ...he UP or DOWN key to change the Filter HOURS Note Check Filter alert can be turned off by setting it to FH 00 00 This is useful for boiler systems without air filters 4 Press the RUN Key and display c...

Страница 15: ...ours the system has been operating will be displayed 4 Program will automatically advance to ULP UV Light Period or ULH UV Light Hours The number of months that has elapsed or hours the system has bee...

Страница 16: ...To remove CFS for UV Light Period or UV Light Hours Press and HOLD YES for 6 seconds until CFS disappears Resets UV Light Period to 0 zero months or UV Light Hours to 1 This also resets Check Filter s...

Страница 17: ...appears in setpoint locations Press again and HOLD until 2n2 appears in setpoint location Press UP or DOWN key to move to desired setting Then press RUN 2nd Stage Differential Settings Please see tab...

Страница 18: ...age Heat 1 0 F 1 0 C Same as 1st Stage 2nd Stg stays energized until 1st Stg satisfied 2n7 for Dual Fuel 1 0 F 50 C Same as 1st Stage VT2007 Only locks out 1st Stage on call for 2nd stage 2n8 for Dual...

Страница 19: ...ash COOL 2 Stage Operation In 1st stage the COOL Icon shines steady In 2nd stage the HI and COOL Icon shines steady For more details of operation see User s Guide in product box page 7 Note When 1st s...

Страница 20: ...at wiring is connected to the correct terminals per wiring diagram Processor possibly spiked by a static discharge Do an FFr Reset Heat Off Cool Switch or Fan Switch stuck or hard to move 99 of time c...

Отзывы: