Installation & Service Manual
Blocked Vent and Flame Roll-Out / Flame
Interlock Switch
BLOCKED VENT SWITCH
INVERTED TO SHOW RESET
UNDERNEATH
DRAFT HOOD
FRONT OF UNIT
Figure 5-7_Blocked Vent Switch Location
HEX FILLER BRACKET
OUTER AIR
DEFLECTOR
DETAIL A
FLAME ROLL-OUT SWITCH /
INTERLOCK SWITCH
UPPER FRONT
JACKET PANEL
LOWER FRONT
JACKET PANEL
Figure 5-8_Flame Roll-Out / Flame Interlock Switch Location
All units are equipped with manual reset blocked vent and
flame roll-out / flame interlock switches. These temperature
switches are located in the controls compartment and in the
relief opening of the boiler’s built-in draft hood. Each switch
has a red reset button. In the event the system has actuated to
shut off the main burner gas supply, wait for the boiler to cool,
then press the red reset to return the boiler to operation. Op er-
a tion of a blocked vent and/or flame roll-out / interlock switch
usually indicates a problem with the venting system, obstruction
of the heat ex chang er flue gas passageway and/or a combustion
air supply prob lem. The cause for operation of the blocked vent
and/or flame roll-out / interlock switch must be determined and
corrected. If the boiler cannot be restored to normal operation,
contact a qualified ser vice in stall er, service agency or the gas
supplier.