UM0026_ASW5000-10000-S-A_EN_V01_0622 21
Procedure:
1.
Switch off the miniature circuit-breaker and secure it against being
inadvertently switched back on.
2.
Shorten L and N by 2 mm each, so that the grounding conductor is 3 mm
longer. This ensures that the grounding conductor is the last to be pulled
from the screw terminal in the event of tensile strain.
3.
Insert the conductor into a suitable ferrule acc. to DIN 46228-4 and crimp
the contact.
4.
Insert the PE, N and L conductor through the AC connector housing and
terminate them into the corresponding terminals of the AC connector
terminal and make sure insert them to the end in the order as shown
,
and
then tighten the screws with an appropriately sized hex key with a
suggested torque of 2.0 Nm.
Damage to the seal of the cover in sub-zero conditions
If you open the cover in sub-zero condition, the sealing of the cover can
be damaged. This can lead moisture entering the inverter.
• Do not open the inverter cover at ambient temperatures lower than -5
℃
.
• If a layer of ice has formed on the seal of the cover in sub-zero
comditions, remove it prior to opening the inverter( e.g. by melting the
ice with warm air ). Observe the applicable safety regulation.