All-in-one solar charge inverter 10
Recommended AC output wiring specifications and circuit breaker selection
Models
Recommended
AC output wiring
diameter
Rated
inverter AC
output
current
Maximum
bypass output
current
Recommended air
switch or circuit breaker
type
HF2420S40-75
6mm2/10AWG
8.6A
30A
2P—40A
HF2420S60-100
6mm2/10AWG
8.6A
30A
2P—40A
HF2420U60-100
8mm2/8AWG
16.7A
40A
2P—63A
HF2430S40-75
6mm2/10AWG
13A
30A
2P—40A
HF2430S60-100
6mm2/10AWG
13A
30A
2P—40A
HF2430U60-100
8mm2/8AWG
25A
40A
2P—63A
Note:
The wiring diameter is for reference only. If the distance between the PV array and the all-in-one
solar charge inverter or the distance between the all-in-one solar charge inverter and the battery is
relatively long, using a thicker wire can reduce the voltage drop to improve system performance.
Note:
The above are only recommended wiring diameter and circuit breaker. Please select the
appropriate wiring diameter and circuit breaker according to actual situations.