background image

Manual Control Setup

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Use the 

,

 and 

.

 

buttons to select 

manu

 for 

manual control. Press the 

;

 button twice to save the selected value and return to the controller main screen.

2. Press the 

 button to access the parameter 

out1

. Use the 

,

 and 

.

 

buttons to set a value 

between 

)0

 and 

10)0 

to control output #1 directly. If the controller has a discrete output, a value of 

2)0 

turns the output on 20% of the time. A value of 

10)0

 would turn the output on 100% of the time. A manually 

controlled analog output value is a percentage of the analog signal. For example, if the controller has a 4-20mA 
current output, a setting of 

)0

 would mean that the output would be 4mA. The output would be 20mA with a 

setting of 

10)0

. Both types of manually controlled outputs are off with a value of 

00

. Press the 

;

  button  

to save the selected value. For dual output control, press the 

 button to access the parameter 

out2

. Use 

the 

,

 and 

.

 

buttons to set a value between 

)0

 and 

10)0 

to control output #2 directly. Press the 

;

 

button twice to save the selected value and return to the controller main screen.

12-11

Error Display Information

15

The chart below shows the possible error displays on the Solo temperature controller. 

Controller Error Display

Display Position

Display

Meaning

Cause

Corrective Action

PV

b160

Cr

Initialization 

PV = Firmware version 

SV = Module type

The controller is 

in the initialization 

process.

The Solo controller displays this information for a few sec-

onds after power up. If the controller continues 

displaying this information, check the input wiring. If the 

problem still exists, replace the sensor or the  controller.

SV

PV

no

Cont

No sensor input

The input terminals 

are open.

Check the input wiring. If the problem still exists, replace the 

sensor or the controller.

SV
PV

Err

Inpt

Input error

The controller cannot 

read the input value

Check the sensor and the input wiring. If the problem still 

exists, replace the sensor or the controller.

SV
PV

Err

Prom

EEPROM error

There is an error with 

the EEPROM

Cycle the power to the Solo controller. If the problem still 

exists, replace the controller.

SV

PV

Flashing PV

PV out of range

The PV is out of 

range

Check the PV range. The parameters 

tp-h

 and 

tp-l

 

define the range. Refer to section 12-1, 12-2 or 12-3 for 

directions on how to access these parameters.

SV

13

Event Inputs

Two event inputs are available with the SL-9696 series temperature controller. (See section 8 for terminal wiring)
EVENT1 input is a normally open contact input that controls the output(s) of the controller. All controller outputs 
are disabled when an external contact for EVENT1 is closed.
EVENT2 input is a normally open contact input that switches the setting value between two different values 
based on the state of the EVENT2. If the contact is open the first setting value is used for all parameters and 
outputs. If the contact is closed the second setting value is used for all parameters and outputs. Each tempera-
ture setting value has individual control parameters.

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Use the 

,

 and 

.

 

buttons to select 

onof

 for 

ON / OFF control and press the 

;

 button to save the selected value. Press the 

 button to access the 

parameter 

s-hC

. Use the 

.

 

button to select 

h2C1

 for controlling a cooling / heating loop. This parameter 

sets the cooling control to output #1 and the heating control to output #2. Press the 

;

 button twice to save 

the value and return to the controller main screen.
2. Press the 

 button to access the parameter 

r-s

. Verify that the default value 

run

 is selected. Press 

the 

;

 button to return to the controller main screen.

3. Press the 

;

 button for less than three seconds to access the 

parameter 

hts

. Use the 

,

 and 

.

 

buttons to enter hysteresis 

for output #2, the heating control. This is the amount the PV must go 
below the SV before the controller output turns on. Press the 

;

 

button to save the selected value. Press the 

 button to access 

the parameter 

Cts

. Use the 

,

 and 

.

 

buttons to enter hyster-

esis for output #1, the cooling control. This is the amount the PV must 
go above the SV before the controller output turns on. Press the 

;

 

button twice to save the selected value and return to the controller 
main screen.
4. Optional regulation parameters can be programmed for additional dual loop control. If this is desired, access 
the regulation mode again by pressing the 

;

 button for less than three seconds. Press the 

 

button 

repeatedly until the parameter 

dead

 appears. Use the 

,

 and 

.

 

buttons to enter a deadband zone 

value around the setpoint where the output is not on. The PV must go beyond the deadband range in order for 
either the heating or cooling output to turn on. Press the 

;

 button twice to save the selected value and return 

to the controller main screen.

Dual Cooling / Heating Loop with ON / OFF Control

12-9

OFF

PV

Set point

ON

Heating

Dead band

Heating hysteresis 

Cooling hysteresis 

Cooling

hts

Cts

dead

Dual loop ON / OFF control 

output operation

Dual Cooling / Heating Loop with PID Control

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Confirm the default value 

Pid

 is selected for PID 

control.  Press the 

 button to access the parameter 

s-hC

. Use the 

.

 

button to select 

h2C1

 for 

controlling a dual cooling / heating loop. This parameter sets the cooling control to output #1 and the heating 
control to output #2. Press the 

;

 button twice to save the value and return to the controller main screen.

2. Press the 

 button to access the parameter 

r-s

. Verify that the default value 

run

 is selected. Press 

the 

;

 button to return to the controller main screen.

3. Refer to Section 12-1 of this Quick Start Guide to set up the PID control parameters.
4. If the temperature controller’s output #1 is discrete, access the regulation mode again by pressing the 

;

 

button for less than three seconds. Press the 

 

button repeatedly until the parameter 

Clpd

 appears. Use 

the 

,

 and 

.

 

buttons to set the time period in seconds for the cooling output control. Press the 

;

 button 

to save the value. If the temperature controller’s output #2 is discrete, press the 

 

button repeatedly until the 

parameter 

hCpd

 appears. Use the 

,

 and 

.

 

buttons to enter the cycle period for output #2, the heating 

output. Press the 

;

 button twice to save the value and return to the controller main screen.

5. Optional regulation parameters can be programmed for additional 
dual loop control. If this is desired, access the regulation mode again 
by pressing the 

;

 button for less than three seconds. Press the 

 

button repeatedly until the parameter 

Coef

 appears. This value allows 

the heating control to have a different proportional setting than the cooling 
loop. The cooling loop proportional band setting is multiplied by the 

Coef 

value to create a proportional band setting for the heating loop 

control. Use the 

,

 and 

.

 

buttons to change this value if desired. 

Press the 

;

 button to save the selected value. Press the 

 

button to 

access the parameter 

dead

. Use the 

,

 and 

.

 

buttons to enter a 

deadband zone value around the setpoint where the output is not effected 
by the proportional control value. As long as the PV remains within the 
deadband zone the output is not affected by the proportional control. The 
integral and derivative controls ignore the deadband setting and may 
cause the output to be on within the deadband zone. Press the 

;

 

button twice to save the value and return to the controller main screen.

12-8

PV

0

Output

Dead band: dead

band width=positive

Set point

Heating

Cooling

dead

PV

0

Output

Dead band: dead

band width=negative

Set point

Heating

Cooling

dead

Dual loop PID control 

positive deadband

Dual loop PID control 

negative deadband

Ramp / Soak Control

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Use the 

,

 and 

.

 

buttons to select 

pro6

 for 

Ramp / Soak control. Press the 

;

 button to save the selected value. Press the 

 button to access the 

parameter 

Patn

. Eight different Ramp / Soak patterns are possible with the Solo Temperature Controller. 

Use the 

,

 and 

.

 

buttons to select pattern number 0 through 7 for programming. Press the 

;

 button 

to save the selected value. 
2. The chart below illustrates an example of a seven step Ramp / Soak pattern (Pattern 0). Press the 

 button 

to access the parameter 

SP00

. Use the 

,

 and 

.

 

buttons to select a setting value temperature for step 

00 and press the 

;

 button to save the value. Press the 

 button to access the parameter 

ti00

. Use 

the 

,

 and 

.

 

buttons to enter a time in hours / minutes for step 00. Follow this procedure until the desired 

number of temperature and time parameters are completed. Press the 

 button to access the parameter 

psx0

. Use the 

,

 and 

.

 

buttons to select the last step to be completed by the Ramp /Soak pattern. For 

example, if 

psx0

 is set to 

4

, steps 00 through 04 will be executed in the pattern.

3. Press the 

 

button to access the parameter 

CYC0

. Use the 

,

 and 

.

 

buttons to select the number 

of additional times the Ramp / Soak pattern will be executed. For example, if 

CyC0

 is set to 

3

, the Ramp / 

Soak pattern will execute a total of four times. Press the 

;

 

button to save the selected value. Press the 

 

button to access the parameter 

lin0

. Use the 

,

 and 

.

 

buttons to choose a Ramp / Soak pattern to 

execute after the completion of Pattern 0. If set to 

off

, the temperature of the last step in Pattern 0 will be held. 

Press the 

;

 

button twice to save the selected value and return to the controller main screen.

100

°

70

°

50

°

30

°

Ramp

03.00

02.00

08.00

Soak

POS0 POS1

POS2

POS3

POS4

POS5

POS6

05.00

03.00

05.00

03.00

Step00 = 50° 
Time00 = 3 hrs 00 min. 
Step01 = 70° 
Time01 = 2 hrs 00 min. 
Step02 = 70° 
Time02 = 5 hrs 00 min.

SP00 
ti00 
SP01 
ti01 
SP02 
ti02 

Step03 = 100° 
Time03 = 3 hrs 00 min. 
Step04 = 100° 
Time04 = 8 hrs 00 min. 
Step05 = 30° 
Time05 = 5 hrs 00 min.

SP03 
ti03 
SP04 
ti04 
SP05 
ti05 

Step06 = 30° 
Time06 = 3 hrs 00 min. 
Process Step = 6 
Cycle times = 0 
Link = OFF

SP06 
ti06  
psx0  
CyCO 
lin0  

12-10

Alarm Outputs

14

Set Value

Alarm Type

Alarm Output Operation

0

Alarm function disabled

Output is OFF

1

Deviation upper and lower limit: 

This alarm output activates when the PV value is higher than the setting value 

SV + ALnH or lower than the setting value SV - ALnL.

ON

OFF

SV - ALnL

SV

SV + ALnH

2

Deviation upper-limit: 

This alarm output activates when the PV value is higher than the setting value 

SV + ALnH.

ON

OFF

SV

SV+ALnH

3

Deviation lower limit: 

This alarm output activates when the PV value is lower than the setting value 

SV - ALnL.

ON

OFF

SV

SV - ALnL

4

Reverse deviation upper and lower limit: 

This alarm output activates when the PV value is in the range of the setting value 

SV+ ALnH and the setting value SV - ALnL.

ON

OFF

SV

SV - ALnL

SV + ALnH

5

Absolute value upper and lower limit: 

This alarm output activates when the PV value is higher than the setting value ALnH or lower than 

the setting value ALnL.

ON

OFF

ALnL

ALnH

6

Absolute value upper-limit: 

This alarm output activates when the PV value is higher than the setting value ALnH

ON

OFF

ALnH

7

Absolute value lower limit: 

This alarm output activates when the PV value is lower than the setting value ALnL

ON

OFF

ALnL

8

Deviation upper and lower limit with standby sequence: 

This alarm output activates when the PV value reaches the set point (SV value) and the reached value 

is higher than the setting value SV + ALnH or lower than the setting value SV - ALnL.

ON

OFF

SV

SV - ALnL

SV + ALnH

9

Deviation upper limit with standby sequence: 

This alarm output activates when the PV value reaches the set point (SV value) and the reached 

value is higher than the setting value SV+ ALnH.

SV + ALnH

ON

OFF

SV

10

Deviation lower limit with standby sequence: 

This alarm output activates when the PV value reaches the set point (SV value) and the reached 

value is lower than the setting value SV - ALnL. 

SV - ALnL

ON

OFF

SV

11

Hysteresis upper-limit alarm output: 

This alarm output activates when the PV value is higher than the setting value  

SV + ALnH. This alarm output is OFF when the PV value is lower than the setting value SV + ALnL.

ON

OFF

SV + ALnL

SV

SV + ALnH

12

Hysteresis lower-limit alarm output: 

This alarm output activates when the PV value is lower than the setting value 

SV- ALnH. This alarm output is OFF when the PV value is higher than the setting value SV - ALnL.

ON

OFF

SV - ALnH

SV

SV - ALnL

13

N/A 

Ramp / Soak Program Alarms

14

This alarm activates when the Ramp / Soak program has ended.

15

This alarm activates while the program is in RAMP UP status.

16

This alarm activates while the program is in RAMP DOWN status.

17

This alarm activates while the program is in SOAK status.

18

This alarm activates while the program is in RUN status.

Note: ALnH includes AL1H, AL2H and AL3H. ALnL includes AL1L, AL2L and AL3L.

*Note: When output #2 is used, ALA3 is disabled. ALA3 is available only for single output loop control.

There are up to three groups of alarm outputs (ALA1, ALA2, ALA3*).  Each alarm group can be programmed for 
one of seventeen different alarm types. To set up the first alarm output, press the 

;

 

button for three seconds. 

Press the 

 

button repeatedly until the parameter 

ALA1

 appears. Use the 

.

 

button to choose the set 

value for the desired alarm type. Refer to the chart below for alarm type information. Press the 

;

 button to 

save the selected value. If additional alarm outputs are required press the 

 

button to proceed to 

ALA2 

and/or 

ALA3

*. Follow the same procedure to program these additional alarms. When the desired alarms are 

programmed, press the 

;

 button repeatedly until the controller returns to the main screen.

The alarm output limits are controlled by the parameters 

Al

n

and 

Al

n

l

, where “n” corresponds to the 

alarm output group chosen. After selecting the desired alarm group(s), press the 

 

button repeatedly until 

the parameter 

Al

n

and/or 

Al

n

appears. Use the 

.

 and 

buttons to enter the high and/or low 

values for each group of alarm outputs selected. Press the 

;

 button to save each selected value. Press the 

;

 button again to return to the controller main screen.

ALA1 and ALA2 are both SPST resistive load 3A @ 250 VAC, normally open relay outputs. ALA3 uses the same 
output as output #2 and is the same type of output.

Содержание SL9696-RRE

Страница 1: ...ungrounded thermocouples Analog input impedance 1 8MΩ Safety Information WARNING To minimize the risk of potential safety problems you should follow all applicable local and national codes that regulate the installation and operation of your equipment These codes vary from area to area and it is your responsibility to determine which codes should be followed and to verify that the equip ment insta...

Страница 2: ...e Down Button Press this key to decrease values displayed on the SV display Hold down this key to speed up the decrement Up Button Press this key to increase values displayed on the SV display Hold down this key to speed up the increment 1 Access the Initial Setup mode by pressing and holding the button for three seconds In the parameter inpt use the and buttons to select the value that correspond...

Страница 3: ...ange 0 50mV Analog Input mv 999 9999 0V 10V Analog Input v10 999 9999 0V 5V Analog Input v5 999 9999 11 3 12 1 12 2 Cooling Loop with ON OFF Control 1 Access the Initial Setup mode by pressing and holding the button for three seconds Press the button repeatedly until the parameter Ctrl appears Use the and buttons to select onof for ON OFF control Press the button to save the value Press the button...

Страница 4: ...e the and buttons to change this value if desired Press the button to save the selected value Press the button to access the parameter dead Use the and buttons to enter a deadband zone value around the setpoint where the output is not effected by the proportional control value As long as the PV remains within the deadband zone the output is not affected by the proportional control The integral and...

Отзывы: