SIG-5600 User Manual Ver. 1.0
- 35 -
5.1
Read/Write
5.1.1
Digital Output Control Register
If the bit corresponding to each port of this register is set to 1, the status of
the output port is turned ON. Conversely, if the bit is set to 0, the status of the
output port is turned OFF. This register is only allowed to write when the port's
output mode is Normal.
Division
Address
Bit
Count
Type
Function Code
HMI Addressing
Example
Port 0
0
1
Boolean
01, 05, 15 or 105
00001
Port 1
1
1
Boolean
01, 05, 15 or 105
00002
Port 2
2
1
Boolean
01, 05, 15 or 105
00003
Port 3
3
1
Boolean
01, 05, 15 or 105
00004
Table 5-8 Digital Output Control Register
5.1.2
Digital Output Pulse Control Register
If the bit corresponding to each port of this register is set to 1, pulses are
output. When the pulse output ends, the corresponding bit is automatically set to 0.
This register is allowed to write only when the output mode of the corresponding
port is Pulse, and cannot be set to 0.
Division
Address
Bit
Count
Type
Function Code
HMI Addressing
Example
Port 0
80
1
Boolean
01, 05 or 15
00081
Port 1
81
1
Boolean
01, 05 or 15
00082
Port 2
82
1
Boolean
01, 05 or 15
00083
Port 3
83
1
Boolean
01, 05 or 15
00084
Table 5-9 Digital Output Pulse Control Register
5.1.3
Reset Digital Input Counter Register
This register initializes the values of Digital Input Counter Register. When the
value of the bit corresponding to each port is stored as 1, the counter value of the
port is initialized and the bit is set to 0 again.
Division
Address
Bit Count
Type
Function Code
HMI Addressing
Example
Port 0
240
1
Boolean
01, 05 or 15
00241
Port 1
241
1
Boolean
01, 05 or 15
00242
Port 2
242
1
Boolean
01, 05 or 15
00243
Port 3
243
1
Boolean
01, 05 or 15
00244
Table 5-10 Reset Digital Input Counter Register