SIG-5440 User Manual Ver. 1.0
- 17 -
connection is terminated. The unit is seconds and can be set between 0 and
3600. Default value is 60
3.2.3
Modbus
⚫
Modbus Type
This item is to set the Modbus type. This product allows the Slave only.
⚫
Unit ID
This item is to set the Unit ID of Modbus/TCP. It can be set between 0 and 247.
The default value is 0.
3.2.4
Digital Input
⚫
Counter Type
This item is to set the counter type of each port. You can choose one among
three options: Rise (rising edge), Fall (falling edge) and Both (rising edge
or falling edge). The default value is Rise.
⚫
Valid Time (Unit: ms)
This item is to set the valid time of input signal. In order for the input
signal to be judged as a valid signal, it must last longer than the time set
in this item. The setting unit is milliseconds; The range is 100 to 30000. The
default value is 100.
⚫
Notify DI Change
This item is to set whether to activate the input port change notification
function. The input port change notification function sends the information to
the master immediately when the status of the input port changes.