The inverter is designed in accordance with the most important international grid-tied 

standards and safety and electromagnetic compatibility requirements. Before delivering to 

the customer, the inverter has been subjected to several tests to ensure its optimal operation 

and reliability.

In case of failure, the LCD screen will display an alarm message. In this case, the inverter 

may stop feeding into the grid. The failure descriptions and their corresponding alarm 

messages are listed in Table 9.1:

6. Remove the 4 screws on the fan plate and pull out the fan assembly slowly.

7. Disconnect the fan connector carefully and take out the fan. 

9. Troubleshooting

8. Maintenance

Alarm Message

OV-G-V01/02/03/04

OV-G-F01/02

UN-G-F01/02

G-IMP

NO-GRID

OV-DC01/02/03/04

OV-BUS

UN-BUS01/02

GRID-INTF01/02

OV-TEM

Failure description

Over grid voltage

Under grid voltage

Over grid frequency

Under grid frequency

High grid impedance

No grid voltage 

Over DC voltage 

Over DC bus voltage

Under DC bus voltage

Grid interference

Over Temperature 

Solution

1.Resistant of AC cable is too high. 
   Change bigger size grid cable
2.Adjust the protection limit if it’s 
   allowed by electrical company.

1.Check connections and grid switch.
2.Check the grid voltage inside inverter 
    terminal.

1.Reduce the module number in series

1.Restart inverter
2.Change power board

1.Check PV input connections
2.Check DC input voltage 
    (single phase >120V, three phase >350V)
3.Check if PV+/

-

 is reversed

Inverter no power 
on LCD

No power 

LCD show initializing 
all the time

Can not start-up

1.Check if the connector on main 
    board or

 

power board are fixed.

2.Check if the DSP connector to 
    power board

 

are fixed.

1.Check inverter surrounding ventilation.
2.Check if there’s sunshine direct on 
    inverter in hot weather.

1.Use user define function to adjust the 
   protection limit if it’s allowed by 
   electrical company.

1.Check inverter inductor connection
2.Check driver connection

UN-G-V01/02

DC-INTF

DC input overcurrent

1.Restart inverter

2.Identify and remove the string to the fault MPPT  
2.Change power board

IGFOL-F

Grid current tracking fail

OV-G-I

Over grid current

OV-DCA-I

IGBT-OV-I

Over IGBT current

1.Restart inverter or contact installer.

IG-AD

Grid current sampling fail

.33.

.32.

8. Clean or replace the fan. Assemble the fan on the rack.

9. C

onnect

 

the

 

electrical

 

wire

 

and

 

reinstall

 

the

 

fan

 

assembly

Restart

 

the

 

inverter

.

Содержание Solis-3P10K-4G-LV

Страница 1: ...o Ltd Ningbo Ginlong Technologies Co Ltd No 57 Jintong Road Binhai Industrial Park Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem...

Страница 2: ...ts 3 3 Keypad 3 4 LCD 5 Installation 5 1 Select Location for the Inverter 5 2 Mounting the Inverter 5 3 Electrical Connections 7 Operation 6 Start Stop 6 1 Start the Inverter 6 2 Stop the Inverter 1 1...

Страница 3: ...r 12K15Kx3 17K20Kx4 User manual x1 Installation and Operation Manual Solis 4G Three Phase Inverter 12 20kW Ver 1 1 Ginlong Ningbo Technologies Co Ltd 1 Introduction 1 Introduction If anything is missi...

Страница 4: ...h the local and national electrical safety standards WARNING Please don t connect PV array positive or negative to ground it could cause serious damage to the inverter CAUTION The PV array Solar panel...

Страница 5: ...ys The keypad is used for Scrolling through the displayed options the UP and DOWN keys Access to modify the adjustable settings the ESC and ENTER keys The two line Liquid Crystal Display LCD is locate...

Страница 6: ...not blocked Exposure to direct sunlight will increase the operational temperature of the inverter and may cause output power limiting Ginlong recommends inverter installed to avoid direct sunlight or...

Страница 7: ...ed hexagon head tapping screws HJ0108 10 50mm fished expandable tubular using the percussion drilling with the 10mm drill need to stay vertically on the wall And the drill hole must be vertically on t...

Страница 8: ...onnection The sign meaning located the bottom of inverter as shown below in table 5 1 All electrical connections are suit for the local or national standard Positive DC input terminal Negative DC inpu...

Страница 9: ...lic clamp to crimp the terminal to the wire see Figure 5 9 Figure 5 9 strip wire Important For multiple inverters in parallel all inverters should be connected to the same ground point to eliminate th...

Страница 10: ...the Inverter The steps to assemble the DC connectors are listed as follows 1 Strip off the DC wire for about 7mm Disassemble the connector cap nut see Figure 5 13 3 Crimp the contact pin to the wire...

Страница 11: ...stic fixture Auxiliary installation Socket element Adapter Seal ring Seal ring thick suit for 12 18mm cable Fastening case Swivel nut Figure 5 22 Connected cable B Clip plastic fixture Auxiliary tight...

Страница 12: ...rter To start up the Inverter it is important that the following steps are strictly followed 1 Switch the grid supply main Switch AC ON first 2 Switch the DC switch ON If the voltage of PV arrays are...

Страница 13: ...ing the ENTER key locks Figure 7 2 a or unlocks Figure 7 2 b the screen b a Figure 7 2 Locks and Unlocks the Screen of LCD 7 Operation 7 Operation Table 7 1 Information list V_DC1 350 8V I_DC1 5 1A V_...

Страница 14: ...ter menu Advanced Info and Advanced settings need password Select Advanced Info from the Main Menu The screen will require the password as below YES ENT NO ESC Password 0000 Figure 7 5 Enter password...

Страница 15: ...ws history of changing settings Only for maintance personel 7 4 7 Communication Data The screen shows the internal data of the Inverter see Figure7 14 which is for service technicians only 01 05 01 25...

Страница 16: ...is function is used to set the new password for menu Advanced info and Advanced information see Figure 7 18 Figure 7 18 Set new password YES ENT NO ESC Password 0000 Enter the right password before se...

Страница 17: ...7 STD setting Solis 4G inverter could set different work mode to work with different grid requirement There are 4 items under STD mode setting 1 Working Mode Set 2 Power Rate Limit 3 Freq Derate Set...

Страница 18: ...r size grid cable 2 Adjust the protection limit if it s allowed by electrical company 1 Check connections and grid switch 2 Check the grid voltage inside inverter terminal 1 Reduce the module number i...

Страница 19: ...erter or connect technician Arcing protection model with AFCI module Detect arc in DC circuit 1 Check inverter connection whether arc exists and restart inverter INI FAULT Initialization system fault...

Страница 20: ...160 850 Start up voltage Volts 180 Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 3 N PE 400 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts...

Страница 21: ...t circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 3 PE 208 220 240 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number Ma...

Отзывы: