7. CONTROL MECHANISMS:
WARNING! Do not load and unhook the control mechanism if disassembled from the fire damper. This is
dangerous for the user and implies mechanism breaking.
WH45 MANUAL VERSION B / M:
• 70°C thermal fuse.
• Manual switch off possible.
• Manual resetting, use the box lever (turn anti-clockwise).
1. Manual switch off button.
2. Control lever.
3. Manual resetting: turn the lever anticlockwise.
WH45 B:
Automatically controlled mechanism with thermal fuse.
Switching off (blade closing):
Manual: Push the off button.
Automatic: When the temperature in the duct exceeds 70°, the thermal fuse melts and the blade closes.
Resetting:
Manual resetting: Turn the lever anti-clockwise.
WH45 M:
Remote controlled mechanism with thermal fuse.
Switching off (blade closing):
Manual: Push the off button.
Automatic: When the temperature in the duct exceeds 70°, the thermal fuse melts and the blade closes.
Remote control: with power supply (input magnet, version MI - MZ ) or power supply interruption (interruption magnet, version
MR - MY). (24V or 230V) electromagnetic coil).
Resetting:
Manual resetting: Turn the lever anti-clockwise.
Note:
For this remote control version, micro switches are fitted as standard.
3
1
2
Solid Air
®
Luchtverdeeltechniek BV Telefoon (020) 696 69 95 Fax (020) 691 30 62 www.solid-air.nl Brandkleppen manual 06 2013
Solid Air
®
Solid Air
®
Luchtverdeeltechniek BV Telefoon (020) 696 69 95 Fax (020) 691 30 62 www.solid-air.nl Brandkleppen manual 06 2013
Solid Air
®
Luchtverdeeltechniek BV Telefoon (020) 696 69 95 Fax (020) 691 30 62 www.solid-air.nl 06 2013
Brandkleppen manual
WH25
WH45
WK25
WK45
Содержание WH45 D
Страница 8: ......
Страница 13: ...12 1MLWH45R0G 12 EC declaration of conformity ...