ERV
TRC800 & TRC800V
3
1.800.961.7370
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
WWW.SOLERPALAU-USA.COM
3
TRC800 & TRC800V INFO
SPECIFICATIONS
NOTE:
Specifications may
be subject to change
without notice.
Unless otherwise specified,
dimensions are rounded
to the nearest eighth of
an inch.
AIRFLOW PERFORMANCE
Motor HP
Phase
External Static Pressure (Inches Water Column)
0.0
0.25
0.50
0.75
.9
1.25
1.50
.75
Single Phase
970 CFM
1,490 Watts
925CFM
1,375 Watts
860 CFM
1,270 Watts
795 CFM
1,160 Watts
750 CFM
1,090 Watts
635 CFM
950 Watts
480 CFM
825 Watts
NOTE:
Watts is for the entire unit (2 motors).
NOTE:
Airflow performance includes effect of clean, standard filter supplied with unit.
ELECTRICAL DATA
HP Volts HZ Phase
FLA
per
motor
Min.
Cir.
Amps
Max.
Overcurrent
Protection
Device
.75
120
60 Single
9.0
20.3
25
.75
230
60 Single
4.5
10.1
15
CORE PERFORMANCE
Thermal
Performance
Ratings
G5
2015.2.xlsx
HE1.5X
(IOM)
30%
50%
70%
90%
300
600
900
1,200
1,500
Ef
fe
ctiv
eness (%)
Airflow (CFM)
At AHRI 1060 standard conditions. See all
AHRI certified ratings at www.ahrinet.org.
TRC800
TRC800V
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range:
250-925 CFM
AHRI 1060 Certified Core:
One L125-G5
Standard Features:
Non-fused disconnect
24 VAC transformer/relay package
Filters:
Total Qty. 2, MERV 8: 20" x 20" x 2"
Unit Dimensions & Weight:
49 1/8" L x 22 1/4" W x 35 7/8" H
210 lbs.
Max. Shipping Dimensions & Weight (on pallet):
63" L x 30" W x 42" H
325 lbs.
Motor(s):
Qty. 2, .75 HP ea., Direct drive blower/standard
motor packages
Ventilation Type:
Static plate, heat and humidity transfer
Typical Airflow Range:
250-925 CFM
AHRI 1060 Certified Core:
One L125-G5
Standard Features:
Non-fused disconnect
24 VAC transformer/relay package
Filters:
Total Qty. 2, MERV 8: 20" x 20" x 2"
Unit Dimensions & Weight:
34 7/8" L x 22 1/4" W x 50 1/8" H
207 lbs.
Max. Shipping Dimensions & Weight (on pallet):
30" L x 42" W x 56" H
325 lbs.
Motor(s):
Qty. 2, .75 HP ea., Direct drive blower/standard
motor packages