The ducting from this fan to the outside of the building has a 

strong  effect  on  the  air  flow,  noise,  and  energy  use  of  the  fan. 

Use the shortest, straightest duct routing possible for the best 

performance, and avoid installing the fan with smaller ducts than 

recommended. Insulation around the ducts can reduce energy 

loss and inhibit mold growth. Fans installed with exisiting ducts 

may not achieve their rated flow.

To ensure quiet operation of ENERGY STAR

®

  qualified  inline  and  remote  fans,  each  fan  shall  be 

installed using sound attenuation techniques appropriate for the installation. For bathroom and general 

ventilation applications, at least 8 feet of insulated flexible duct shall be installed between the exhaust or 

supply grille(s) and the fan. For remote ventilation applications, where metal duct is generally required 

by code, a metal sound attenuator shall be installed between the hood and the fan.

5.    ELECTRICAL CONNECTION

All TD-SILENT series fans operate from a standard 120V, 60Hz AC electrical supply. All wiring must 

be carried out in accordance with National Electrical Code and all applicable state and local buildings 

codes.

Electrical connections should be made in accordance with the following diagram: 

See Figure (3)

3.     ENVIRONMENT

The TD-SILENT series of fans are suitable for operation within indoor environments only. 

The TD-SILENT units are suitable for the exhaust or supply of both conditioned and un-

conditioned airstreams within the temperature ranges. Size 125XS and 200S are suitable 

for working airstreams up to 104 deg F (40C), whereas sizes 150S is suitable for working airstreams 

up to 140 deg F (60C).

4.    MOUNTING

The TD-SILENT series can be mounted in any orientation, horizontal or vertical, and is suitable 

for numerous types of applications. 

See Figure (1)

. Illustration of some typical applications. If the 

installation is made  to  rigid or flexible  ducting,  then  we  would  recommend  the  correct  diameter  

ducting  is used to couple to the fan flanges. If it is necessary to bend the duct at the discharge of the 

fan, then the bend radius should be as large as possible.

All models include a robust mounting bracket which enables easy and quick installation of the fan. 

See 

Figure (2) 

Installation Diagrams For TD-MIXVENT Duct Fans.

Seal penetrations, duct, and fan with duct fast clamps, duct tape, or other similar material (available 

through your local distributor) to create an air-tight path from the ventilated space to the building exterior. 

Use flexible or rigid insulated duct and wrap the fan with insulation where allowed by code in order to 

reduce: heard noise, building heat loss/gain, and condensation.

Duct

Tape

Tape

Duct

Fan

Model

Recommended 

Round Duct Size (in.)

TD-125XS

5”

TD-150S

6”

TD-200S

8”

Содержание TD-SILENT SERIES

Страница 1: ...SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by S P These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures because of the wide variety and types of fans manufactured by S P ...

Страница 2: ...hen cutting or drilling into wall or ceiling do not damage electrical wiring and other hidden utilities 6 Ducted fans must always be vented to the outdoors 7 If this unit is to be installed over a tub or a shower it must be marked as appropriate for the application and connected to a GFCI Ground Fault Circuit Interrupter protected branch circuit 8 Never place a switch where it can be reached from ...

Страница 3: ...LENT series of fans are suitable for operation within indoor environments only The TD SILENT units are suitable for the exhaust or supply of both conditioned and un conditioned airstreams within the temperature ranges Size 125XS and 200S are suitable for working airstreams up to 104 deg F 40C whereas sizes 150S is suitable for working airstreams up to 140 deg F 60C 4 MOUNTING The TD SILENT series ...

Страница 4: ...USE any detergents or abrasive materials for cleaning Figure 2 Installing TD SILENT SERIES Models TD 125XS TD 150S and TD 200S 1 To install the TD SILENT models the fan motor wheel assembly must first be removed Unlock the two flanges around the casing and remove 2 Secure the mounting bracket fan flange assembly to a fixed structure 3 Replace the fan motor wheel assembly and tighten the two flange...

Страница 5: ...g the nature of the fault THE FOLLOWING WARRANTIES DO NO APPLY Damages from shipping either concealed or visible Claim must be filed with the carrier Damages resulting from improper wiring or installation Damages caused by acts of nature or resulting from improper consumer procedures such as Improper Maintenance Misuse Negligence Alteration Abuse Abnormal Use or Accident or Incorrect Electrical Vo...

Страница 6: ... terminate one 1 year after the shipment of said products and parts In no event whether as a result of breach of contract or warranty or alleged negligence defects incorrect advice or other causes shall seller be liable for special or consequential damages including but not limited to loss of profits or revenue loss of use of the equipment or any associated equipment cost of capital cost of substi...

Страница 7: ...7 ...

Страница 8: ...8 ...

Отзывы: