10
8. Operation Interface.
8.1. Control
-
Initial voltage at Start and voltage rise (Start) / reduction time (Stop) set by 3 built-in
potentiometers or via Modbus communication channel.
- Start / Stop command supplied by external voltage free contact or via
Modbus communication channel.
- Fault reset can be done by switching control voltage OFF / ON or via
Modbus communication channel.
8.2. Control terminals
#
Name
Duty
1
L
Control voltage (100-240Vac) phase input
2
N
Control voltage neutral input
3
Start / Stop
Connect 100-240Vac related to N to start the motor.
Disconnect – to stop the motor.
4
Run relay NO
Closed in Start and Run or only Run state of the starter.
5
Run relay common
6
Fault relay NO
Closed in Fault state of the starter.
7
Fault relay common
8
RS485 A-Line (+)
RS485, Modbus communication port.
9
RS485 B-Line (-)
10
Ground