NO VOLTAGE AT THE L+ AND L- TERMINALS
Note: To bypass all remote switching circuits, disconnect all wires from the
sensor interface terminal block in the controller housing (the small terminal
block) and switch program switches #5 and #6 to the OFF position.
1. Make sure the system ON/OFF switch is ON.
2. Check to see if the water level is above the top electrode when low water
cut-off circuit is being used.
3. Check to see if the float switch, if used, is functioning properly.
4. Check the controller for proper programming and adjustment. If the voltage
setting on the controller is higher than the incoming voltage, the controller
will not turn on, (See controller adjustment section)
Make sure the Yellow LED (over-current shut down) is not on. If it is, switch
OFF the system ON/OFF switch, wait a minute and then switch it ON.
EXCESSIVE CURRENT DRAW (More than the rating of the pump, but less than
the rating of the controller)
1. Check wiring diagram for proper connection.
2. Check for skinned wires or faulty underwater splice.
3. Check for locked motor armature. With the pump out of the well, bypass the
controller and connect power directly to the motor leads. If the pump still
does not run and the current is over 1.5 amps, the pump is in a locked rotor
condition and must be repaired.
5.0 Technical Specifications
6.0 Warranty Statement
PCA and PCB Series of Pump Controllers
Limited Warranty - Twenty Four Months
Solarjack warrants to the original consumer that its products shall be free from defects in
material and workmanship under normal applications and service conditions for a period
of twenty four (24) months after the original date of purchase, but not to exceed thirty (30)
months from the date of manufacture.
At its option, Solarjack will repair or replace the Solarjack product that proves to be
defective within such warranty period. This limited warranty shall not apply if the
Solarjack product has been damaged by unreasonable use, accident, negligence,
shipping, service or modification by anyone (other than by Solarjack), or failure which are
caused by products not manufactured by Solarjack, or should the products serial number
be altered, or by damage that is attributable to an act of God, or by any other causes
unrelated to defective materials or workmanship.
The original purchaser MUST complete and send in the warranty registration card, with
the pump serial number and the controller serial number for warranty validation. No