3. Pressure increasing

A. 

Pressure increasing with draining and charging of previously determined volume of fluid

 

 

1. Fill the solar system as described in previous chapter. Calculate the volume of fluid inside 

the solar system 
2. Determine the Discharge Volume from the right column of the table below

B.  Pressure increasing with air compressor 

 

1. Ensure the solar thermal circuit is properly filled with glycol/water mixture, as previously 

described 

2. Close all valves. Connect the Air Compressor to Leaking Valve.

 

3. Make sure the pressure in compressed air is bigger than the pressure in solar circuit.  

4. Slowly, partial open the Leaking Valve and add compressed air slowly until system 

pressure increases for 0,5 bars. 

5. Close the Leaking Valve.

 

6. System is ready to run.

3. Open the Filling Valve, open Leaking Valve and Discharge previously detemined volume.
4. Close the Leaking Valve.

5. Fill the discharged volume back into the solar system.
6. Pressure is increased. 

In order to avoid vacuum appearance during the pump operating, it is important to add 0,5 bars to 

the filled system. There are two ways to do it:

Volume of fluid filled in the solar system

Discharge Volume

20 l

10 l

21 l ÷ 40 l

20 l

41 l ÷ 60 l

30 l

61 l ÷ 80 l

40 l

81 l ÷ 100 l

50 l

Содержание UniQube

Страница 1: ...1 UniQube Drain Back Reservoir Installation and Operation Manual Read and understand this manual before installation commisioning and operation...

Страница 2: ...hen product is in operating mode some parts of it may reach temperature over 51 C It can cause severe burns instantly or death from scalds Children disabled and elderly are at highest risk of being sc...

Страница 3: ...L 650mm Setup and operation procedure The following instructions describe a fast and simple way to commissioning the installation 1 Installation of reservoir and pipe connecting Install the reservoir...

Страница 4: ...once complete filling Idle 2 cm m 2 inclination 5 cm m 5 inclination 5 cm m 5 inclination A B C E I J F G N M Drain Back reservoir UniQube Solar Panels filled Pump On In Operation 2 cm m 2 inclination...

Страница 5: ...Heat Exchanger volume is declared in the technical data of the UniQube hot water tanks The volume of copper or corrugated stainless steel pipes can be read on page 7 Filling Valve pump and Safety Valv...

Страница 6: ...sure the pressure in compressed air is bigger than the pressure in solar circuit 4 Slowly partial open the Leaking Valve and add compressed air slowly until system pressure increases for 0 5 bars 5 C...

Страница 7: ...29m X UniQube DB 440 Liters X 48m 26m 20m 15m Useful notes for the installers The following table shows what is the maximum allowed pipe lenght for your solar thermal drain back system depending on wh...

Страница 8: ...uroterm d o o Lece Koteski 50 Industrial area Biljana Prilep Republic of North Macedonia tel 389 48 419 415 fax 389 48 422 981 e mail info solarico eu GUARANTEE Type Serial number Guarantee Manufactur...

Отзывы: