35
L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40,
L15US-IB60 L15US-IB00, L20US-IB60, L20US-IB00 UPS
negative ones. The user can choose the capacity and the numbers of the batteries according
to their desire.
External battery connections for long-run units.
Figure 27 External battery connections for long-run units
NOTE!
The BAT+ of the UPS connect poles is connected to the anode of the positive
battery, the BAT-N is connected to the cathode of the positive battery and the
anode of the negative battery, the BAT- is connected to the cathode of the
negative battery.
L10US&L15US&L20US-IB00 of long-run units: Factory setting is battery
quantity---20pcs, battery capacity---12V/40Ah (charger current 6A). When
connecting 18/20/22/24/26 batteries, please re-set desired battery quantity and
its capacity after UPS starts at AC mode. Charger current could be adjusted
automatically according to battery capacity selected. All related settings can be
done through LCD panel or monitoring software.
CAUTION!
Ensure correct polarity battery string series connection. I.e., inter-tier and inter
block connections are from (+) to (-) terminals.
Do not mix batteries with different capacity or different brands, or even mix up
new and old batteries, either.