UPS for 208 Vac Grid, B120US Installation Guide, doc. rel. 3.0
3.3.4.4.
Connecting the UPS to the electrical panel
When connecting the electrical panel to The Gamatronic UPS, a torque of 10 to 20 Nm is
recommended on the UPS terminal side. The lug size needed to fit a 3/8" or metric M10 screw
size.
Suitably rated circuit breakers must be installed between the UPS and the electrical panel.
A suitably rated fuse must be installed on the rectifier ac input line and bypass input line.
For system connections refer to Figure 9 or Figure 10; for circuit breaker
recommendations, refer to Table 4.
For an overview of circuit breaker selectivity, refer to Chapter
Warning: Connection of The UPS to the electrical panel must be
performed only by a licensed electrician experienced with similar
systems.
Warning: If two separate input lines are used for rectifier and bypass
input (as in Figure 9 and Figure 10), the Neutral line must be shared.
following
warning:
WARNING: The recommended cable and breaker sizes are based on
optimal installation conditions. Local code must be followed to coincide
with the site ambient temperatures, wire insulation type, conductor
material, length of cables, method of installation and voltage drop
requirements.
Table 4: Recommended circuit breakers for the current rating for 20-120kva 208v UPS
UPS
MODEL
*
MAIN SWITCH
SW1
**
MAIN CB
CB1 (with
TRANSFORMER)
RECTIFIER CB
CB2
BYPASS & OUTPUT
CB,
CB3, CB4, CB5
Use copper wires only!
18KW
3x63A
3x63A
3x63A
3x56A
4 AWG
36KW
3x133A
3x133A
3x133A
3x112A
2/0 AWG
54KW
3x200A
3x200A
3x200A
3x167A
4/0 AWG
72KW
3x267A
3x267A
3x267A
3x223A
350 kcmil/2 x 2/0 AWG
90KW
3x333A
3x333A
3x333A
3x278A
400 kcmil/2 x 3/0 AWG
108KW
3x400A
3x400A
3x400A
3x333A
500 kcmil/2 x 4/0 AWG