Operation manual of solar water controller SR530C8/SR530C8Q 
 

 

--------------------------------------------------------------------------------------------------------------------------------------------------- 

- 32 - 

 
 
 

Setup steps: 

To access main menu FUN, then select submenu BYPR, “BYPR------” displays on 
screen.   
►Press “SET” button, “- - -”blinks on screen, 
default set is “OFF” 
►Repress “SET” button, to activate by-pass 
function, “BYPR 80

” displays on the screen, “80

” blinks   

►Press “+”“-” button to adjust this parameter, adjustable range (5

℃~

120

► Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically, 
parameters are saved automatically. 
 

This signal displays on the screen, it indicates by-pass function is 
activated.   

 

4.7 HND Manual mode 

When using this controller first time or when debugging this controller, output of this 
controller 

R1

R2

R3

R4

can be triggered manually. “On, OFF” control. 

 

Setup steps: 

To access main menu HND,   
►Press “SET” button, “HND1 off” displays on the screen, R1 output manually set   
►Repress “SET” button, “HND1 on” 
displays on the screen, R1 output is 
switched-on 
►Repress “SET” again, “HND1 off” 
displays, R1 output is switched-off   
►Press “ESC” to exit R1 set program 
 

------------------------------------------------------------------------------------------------------------------ 

►Press “+” button, “HND2 off” displays on 
the screen, R2 output manually set 
►Press “SET” button, “HND2on” displays on 
the screen, R2 output is switched-on 
►Repress “SET” again, “HND2off” displays, 
R2 output is switched-off   
►Press “ESC” to exit R2 set program 

Содержание SR530C8

Страница 1: ...cience and Technology Create Perfection Read the instruction carefully please before operation Installation and Operating Manual SR530C8 SR530C8Q Solar Controller For Split Pressurized Hot Water Syste...

Страница 2: ...ubmenu 13 4 3 Main menu DT O DT F Temperature difference function 14 4 4 Main menu THET timing heating 15 4 5 TEMP Temperature main menu 18 4 5 1 EM Emergency collector temperature emergency switch of...

Страница 3: ...4 6 5 2 tRUN Pump running time 31 4 6 6 BYPR High temperature by pass function tank temperature automatically adjusting 31 4 7 HND Manual mode 32 4 8 PASS Password setting 33 4 9 LOAD Recovery to fac...

Страница 4: ...ialists 1 2 About this manual This manual describes the installation function and operation of a solar thermal controller When installing the remaining components e g the solar collectors pump assembl...

Страница 5: ...ked the text and pictures of this manual and provided the best of our knowledge and ideas however inevitable errors maybe exist Please note that we can not guarantee that this manual is given in the i...

Страница 6: ...compliance with the provisions of the installation For example switch or fuse please note that it should be separated between the wires and use AC power 2 1 Installing the controller Note the control...

Страница 7: ...ng installation Depending on the type of installation the cables may enter the device through the rear hole of the case or the lower side hole of the case Cable come from the rear remove the plastic f...

Страница 8: ...3 and T4 for NTC10K B 3950 sensors used for measuring the temperature of tank and pipe Advice regarding the installation of temperature sensors Only original factory equipped Pt1000 temperature sensor...

Страница 9: ...ntrol max switching current 1A Output R2 for hot water circuit pump electromagnetic relay and max switching current 3 5A R2 ports are always open Output R3 for by pass circuit pump or valve electromag...

Страница 10: ...ntroller SR530C8 SR530C8Q 9 Press button to set week Press ESC button to exit set program or wait for 20 seconds to exit program automatically Code Week day MO Monday TU Tuesday WE Wednesday TH Thursd...

Страница 11: ...of solar water controller SR530C8 SR530C8Q 10 3 2 Menu structure Menu of controller SR530C8Q Menu of controller SR530C8 Submenu Through submenu customer can set the parameter as desired value please c...

Страница 12: ...of collector SMX Maximum temperature of tank REC Tank re cooling function C F Celsius and Fahrenheit temperature transferring FUN Auxiliary function DVW G Anti legionnaires function CIRC Temperature c...

Страница 13: ...n as the switch on temperature difference Ton between the collector array T1 and the storage tank T2 is reached If the temperature difference between the collector array T1 and storage tank T2 drops b...

Страница 14: ...k for entering password factory default set password is 0000 Press button to enter first digital of password Press SET button again the second digital blinks Press button button to enter second digita...

Страница 15: ...ommend to use default set Switch on and switch off DT are alternating set To avoid mistake the minimum difference between two temperature differences Ton Toff is set as 2 o C Setup the switch on tempe...

Страница 16: ...ure adjustable range 10 OFF 2 The switch off temperature adjustable range ON 2 80 If you want to shut off one timing heating then you can set the turning on time and turning off time same value for ex...

Страница 17: ...n be set Press SET button 05 of hour time blinks on screen Press button to adjust hour of time Repress SET button 00 of minute time blinks on screen Press button to set minute of time Repress SET butt...

Страница 18: ...Repress SET button 00 of minute time blinks on screen Press button to adjust minute of time Repress SET button temperature 50 blinks on screen Press button to adjust switch on temperature of heating P...

Страница 19: ...the parameters can be adjusted in a solar system Following submenu can be access though TEMP main menu EM Emergency collector temperature Emergency switch off temperature of collector 4 5 1 CMX Maxim...

Страница 20: ...temperature adjustable range 120 200 factory set is 130 Repress SET button activate and deactivate this function if deactivate the function EM displays on screen Press ESC button to exit menu or wait...

Страница 21: ...MX CMX 110 displays on screen Press SET button parameter 110 blinks Press button to adjust the collector protection temperature adjustable range 100 190 factory set is 110 Repress SET button activate...

Страница 22: ...rcuit pump is triggered Besides when tank temperature T2 drops to 4o C electrical heater is triggered automatically and it is in operation until T2 is heated up to 20 o C or it is stopped when program...

Страница 23: ...sed even at the case that DT caters condition When tank temperature drops and is 2o C below the SMX solar pump restarts when DT caters condition Setup steps To access main menu TEMP then select submen...

Страница 24: ...s on screen Press SET button parameter blinks on the screen Press button to select between Celsius and Fahrenheit temperature factory set is Press ESC button to exit menu or wait for 20 seconds to exi...

Страница 25: ...n of anti freezing liquid 6 4 3 INTV Pump interval function 4 6 5 tRUN Pump interval time 4 6 5 1 tSTP Pump running time 4 6 5 2 BYPA High temperature by pass function tank temperature automatically a...

Страница 26: ...temperature is 40o C when return temperature T4 drops to 35o C circulation pump R2 is triggered when T4 rises up to 40o C circulation pump R2 is ceased Condition for triggering hot water circulation p...

Страница 27: ...teps To access main menu FUN then select submenu nMIN nMIN 30 displays on screen Press SET button parameter 30 blinks on the screen Press button to adjust speed of circuit pump adjustable range 30 100...

Страница 28: ...en Press button to adjust increase rate of RIS of temperature difference adjustable range 1 20 factory set is 1o C Press ESC button to exit the menu or wait for 20 seconds to exit automatically parame...

Страница 29: ...or 3 seconds buzzer makes 3 times du the daily thermal energy is cleared and daily thermal energy is reset to 00 Press button select to check accumulative thermal energy KWH XX or MWH XX SET displays...

Страница 30: ...ycol 03 Tyfocor LS G LS Setup steps To access main menu FUN then select submenu MEDT MEDT 01 displays on screen Press SET button parameter 01 blinks on the screen Press button to adjust type of heat t...

Страница 31: ...me is 06 00 20 00 During the period that solar pump is in operating the period of running time can be set by parameter tRUN controlled check the temperature signal of sensor if the temperature increas...

Страница 32: ...range 5 120 seconds Press ESC button to exit the menu or wait for 20 seconds to exit automatically parameters are saved automatically 4 6 6 BYPA High temperature by pass function tank temperature auto...

Страница 33: ...by pass function is activated 4 7 HND Manual mode When using this controller first time or when debugging this controller output of this controller R1 R2 R3 R4 can be triggered manually On OFF control...

Страница 34: ...on displays on the screen R4 output is switched on Repress SET again HND4 off displays R4 output is switched off Press ESC to exit R4 set program Note when manual mode is activated signal displays on...

Страница 35: ...20 seconds to exit automatically Warning If the password is forgot it is not possible to recover but you can recover the password to factory set then you can reedit a password like above descript step...

Страница 36: ...perature drops 8 o C below the storage tank temperature T2 solar circuit pump starts to work when the temperature of collector is 2o C below the tank temperature and solar circuit pump is ceased Activ...

Страница 37: ...ature adjustable range 10 80 factory set is 60 After 20 seconds this function is activated signal displays on the screen and heating signal blinks also Press Heating button again to switch off manual...

Страница 38: ...will start the anti dry heating protection EE displays on screen and controller switches off all outputs H1 In this case it ought to switch off power supply check and resolve the problems and then swi...

Страница 39: ...en Meaning Cause of error Error rectification T0 T0 sensor problem Sensor wiring interrupted not connected or short circuit Check resistance value replace Thermal measuring function is switched on T0...

Страница 40: ...p doesn t operate despite the fact that switch on conditions are satisfied The pump symbol in the display blinks Pump power supply is interrupted Check the pump power cable Pump doesn t operate The pu...

Страница 41: ...eviation 1 is acceptable PT1000 resistance value 0 10 20 30 40 50 60 70 80 90 100 110 120 1000 1039 1077 1116 1155 1194 1232 1270 1309 1347 1385 1422 1460 NTC 10K B 3950 resistance value 0 10 20 30 40...

Страница 42: ...Suitable power of pump 3 600W 3 600W Suitable power of electrical heater 1 2000W 1 2000W Inputs 2 x Pt1000 sensor 500o C for collector silicon cable 280o C 3 x NTC10K B3950 sensor 135o C for tank PVC...

Страница 43: ...llector high accuracy PT1000 sensor A01 Parameter PT1000 6X50mm Sensor for tank high accuracy NTC 10K sensor A02 Parameter NTC10K B 3950 6X50mm Thermowell of sensor stainless thermowell A05 Parameter...

Отзывы: