INSTALLATION  MANUAL

  

 

 

  

Advanced Lithium-Ion battery

  

 

 

 

 

SS4074-11

Содержание SS4074-11

Страница 1: ...Solar MD PTY ltd Unit 23 Alternator Park Montague Gardens 7441 Cape Town South Africa INSTALLATION MANUAL Advanced Lithium Ion battery SS4074 11...

Страница 2: ...Information 3 Warnings Cautions 3 Specification 4 Mechanical installation 5 Installing bottom cover plate 6 Electrical installation 7 Commissioning 9 Multicolor multipurpose button 10 Button function...

Страница 3: ...s The rated voltage is 51 2V nominal to suit 48V systems WARNING Read the entire document before installing or using the Solar MD battery Failure to comply with the instructions or warnings in this do...

Страница 4: ...hen using Warnings Cautions For communication and other information please read the BMS manual Do not attempt to disassemble repair modify or tamper with this battery unit Do not insert foreign object...

Страница 5: ...Mechanical relay NO Rated Current Ampere 100A C Rating 0 69C Number of battery modules 1 module Com CANBUS isolation Yes 1 5kV Weight Transportation protection Yes Operating voltage 44 8V 55 6Vdc Indi...

Страница 6: ...o za T 021 555 2181 Mechanical installation Please use the correct mounting screws for the correct wall surface Screw heads should not be larger than 16mm in diameter The Battery is only to be install...

Страница 7: ...1 Installing bottom cover plate The Battery comes with two covers for single out or double out on both sides of the battery Use the 1 or 2 way out cover plate and fix it with the two M5x6 bolts provid...

Страница 8: ...Africa Solar MD PTY ltd E info solarmd co za T 021 555 2181 Electrical installation Step 1 Before connecting anything be sure that the battery ON OFF switch is at OFF 7 Figure 4 BMS boardcomponent loc...

Страница 9: ...citors inside the connected device This can be harmful for people Connecting main battery terminal must be with correct size cable based on the rated current of the battery and the charger inverter in...

Страница 10: ...rence is in safe ranges under 2 5V Caution A hot connection with difference in voltage can cause very high equalization current which can burn the fuses of the battery Caution Measure the voltage of t...

Страница 11: ...uously after function 6 shutdown mode is activated and the battery will send a signal to switch off in 4sec Further holding the button causes the BMS to delay complete shutdown for a maximum of 3 minu...

Страница 12: ...scharge represents the opposite from charge study color for 1 interval and slow loss of color following illumination interruption Solar MD users refer for both as charging discharging waves When this...

Страница 13: ...low and direction c Off The functionality of the indication LEDs are configurable see more on this multifunction push button 2 If the Warning LED is Orange a The indication LEDs will show the warning...

Страница 14: ...er than the maximum allowed electrical discharging current 4 Override ON active protection is forced to work at extreme levels for preset period 5 Override OFF active protection is forced to switched...

Страница 15: ...g shutdown in 3sec 12 Battery Protection in critical stage Override mode reached the maximum permitted values pending shutdown in 3sec 13 Battery Protection in critical stage Normal mode reached the m...

Страница 16: ...o high 23 Internal error Additional information on request 24 Internal error Additional information on request 25 Internal error Additional information on request 26 Internal error Additional informat...

Страница 17: ...o high 23 Internal error Additional information on request 24 Internal error Additional information on request 25 Internal error Additional information on request 26 Internal error Additional informat...

Страница 18: ...o high 23 Internal error Additional information on request 24 Internal error Additional information on request 25 Internal error Additional information on request 26 Internal error Additional informat...

Страница 19: ...cting other device operating at different speed rate is not TheoutputoftheBms EX CANtransceiveris galvanically isolated RJ45 connections can be used for daisy chaining BMS EX together using a straight...

Страница 20: ...ermination resistor set 1 CAN BUS line in initialization stage Canbus init occur when the line was opened and then established Minimum period for initialization is 30sec In this period all nodes are s...

Страница 21: ...urrent has been achieved The BMS will restart automatically please contact support team or approved installer 21 The BMS is set for different number cells in series as the actually installed Contact y...

Страница 22: ...on function are disalled then verify if there is a voltage difference on the inverter display and the battery terminals 0 3C discharge charge current If so adjust the values above Please check if your...