Solair J17A2 Скачать руководство пользователя страница 21

Manual 2100-588A 

Page 

21 of 29

TROUBLESHOOTING

FIGURE  11

FAN BLADE SETTING

TABLE  1

FAN BLADE DIMENSION

R-410A

REFRIGERANT CHARGE

This unit was charged at the factory with the quantity of 
refrigerant listed on the serial plate.  AHRI capacity and 

efficiency ratings were determined by testing with this 

refrigerant charge quantity.

The following pressure tables show nominal pressures 

for the units.  Since many installation specific situations 

can affect the pressure readings, this information should 

only be used by certified technicians as a guide for 

evaluating proper system performance.  They shall not 
be used to adjust charge.  If charge is in doubt, reclaim, 
evacuate and recharge the unit to the serial plate charge.

REMOVAL OF FAN SHROUD

  1. Disconnect all power to the unit.

  2. Remove the screws holding both grilles, one on 

each side of unit, and remove grilles.

  3. Remove screws holding fan shroud to condenser 

and bottom.  Nine (9) screws.

  4. Unwire condenser fan motor.

  5. Slide complete motor, fan blade, and shroud 

assembly out the left side of the unit.

  6. Service motor/fan as needed.

  7. Reverse steps to reinstall.

TABLE  2

REFRIGERANT CHARGE

TABLE  3

REFRIGERANT CHARGE

The suction line temperatures in Table 4 above are 
based upon 80°F dry bulb / 67°F wet bulb (50% R.H.) 

temperature and rated airflow across the evaporator 

during cooling cycle.

The correct system R-410A charge is shown on the unit 
nameplate.  Optimum unit performance will occur with 
a refrigerant charge resulting in a liquid subcooling as 
shown in Tables 2 & 3.  If charge is in doubt, reclaim and 
recharge to factory nameplate charge.

"A"

AIRFLOW

MIS-1724

Model

Dimension

A

J17A2 / J17L2

J24A2 / J24L2

1.00"

J30A2 / J30L2

J36A2 / J36L2

1.25"

J42A2 / J42L2

J48A2 / J48L2

J60A2 / J60L2

J70A2 / J70L2

1.75"

Model

Rated 

Airflow

95°F OD 

Temperature

82°F OD 

Temperature

J24A2 / J24L2

800

56 - 60

56 - 60

J30A2 / J30L2

1000

57 - 61

57 - 61

J36A2 / J36L2

1100

56 - 60

57 - 61

J42A2 / J42L2

1400

58 - 62

60 - 64

J48A2 / J48L2

1550

63 - 67

65 - 69

J60A2 / J60L2

1650

63 - 67

64 - 68

Model

Rated 

Airflow

95°F OD 

Temperature

82°F OD 

Temperature

J17A1 / J17L1

550

18 - 21°

19 - 22°

J70A1 / J70L1

1800

15 - 18°

16 - 19°

FAN BLADE SETTING DIMENSIONS

Shown in Figure 11 is the correct fan blade setting for 
proper air delivery across the outdoor coil.  Refer to 

Table 1 for unit specific dimension.

Any service work requiring removal or adjustment 
in the fan and/or motor area will require that the 
dimensions below be checked and blade adjusted in or 
out on the motor shaft accordingly.

Содержание J17A2

Страница 1: ...LLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS J17A2 J17L2 J24A2 J24L2 J30A2 J30L2 J36A2 J36L2 J42A2 J42L2 J48A2 J48L2 J60A2 J60L2 J70A2 J70L2 Manual 2100 588A Supersedes 2100 588 F...

Страница 2: ...flow 25 Table 8 Indoor Blower Performance 25 Table 9 Maximum ESP Electric Heat Only 25 Table 10 Electric Heat 26 Table 11A Optional Accessories Right Hand 27 Table 11B Optional Accessories Left Hand 2...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...rticularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local...

Страница 5: ...ch Any grille that meets with 5 8 inch louver criteria may be used It is recommended that Bard Return Air Grille Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used Conta...

Страница 6: ...ING THE UNIT 1 These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides A bottom mounting bracket attached to skid for shipping is provided for...

Страница 7: ...ce Electrical Built In Ventilation Air models Electrical 4 Pitch Filter Access Panel Top Rain Low Voltage Electrical Entrance Standard flush vent door for Access Panel Lockable non ERV Econ Disconnect...

Страница 8: ...IME OF INSTALLATION OPENING MIS 3157 ENTIRE LENGTH OF TOP RETURN AIR DUCT Wall Opening and Hole Location View Right Side View OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RA...

Страница 9: ...TES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEATER...

Страница 10: ...1 4 1 1 4 29 3 4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM...

Страница 11: ...ir duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could resu...

Страница 12: ...FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR AC...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...ot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups See Tables 5 6 f...

Страница 15: ...EAT STAGE 2 ECONOMIZER STAGE 1 VENTILATION IF EQUIPPED N O CONTACT COMPRESSOR OPEN OR SPECIAL USE AS REQUIRED 24V HOT FAN BLOWER ALARM RELAY N C CONTACT ELECTRIC HEAT STAGE 1 J MODULE REFRIGERANT IF E...

Страница 16: ...TO R AND RT TERMINALS OPEN OR SPECIAL USE AS REQUIRED N C CONTACT COMPRESSOR ECONOMIZER STAGE 1 BLUE COMMON BLACK ALARM RELAY ELECTRIC HEAT STAGE 1 ORANGE FACTORY INSTALLED JUMPER REMOVE FOR 2 STAGE...

Страница 17: ...INPUT USED IF MINIMUM YELLOW RED 2 1 POSITION REQUIRED FOR VENTILATION BLACK PINK BROWN WHITE ORANGE 24V TRANSFORMER OUTPUT YELLOW FACTORY INSTALLED JUMPER REMOVE FOR 2 STAGE OPERATION RED PURPLE BLU...

Страница 18: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 19: ...rrect phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation...

Страница 20: ...e manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardl...

Страница 21: ...T CHARGE TABLE 3 REFRIGERANT CHARGE The suction line temperatures in Table 4 above are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator during cooling...

Страница 22: ...35 356 138 380 141 405 143 431 145 457 147 484 149 512 151 540 152 569 154 599 J36A L 75 62 Low Side High Side 120 339 122 366 124 392 126 418 129 446 130 473 132 501 134 529 135 558 136 586 80 67 Low...

Страница 23: ...or 2 24 32 47 58 84 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 J30A2 B00 B0Z B06 B09 B15 230 208 3 1 1 1 1 18 24 33 51 20 25 35 60 12 10 8 6 12 10 10 10 J30A2 C00 C0Z C06 C09 C15 4...

Страница 24: ...56 30 30 50 60 10 10 8 6 10 10 10 10 J24L2 B00 B0Z B06 230 208 3 1 1 15 22 20 25 12 10 12 10 J24L2 C00 C0Z C06 460 3 1 1 9 11 15 15 14 14 14 14 J30L2 A00 A0Z A05 A08 A10 A15 230 208 1 1 1 1 1 1 or 2 2...

Страница 25: ...85 1415 1275 955 925 1850 1800 1605 1555 2080 2015 1505 1460 2050 1845 1490 1400 0 1 1010 970 730 715 945 925 1305 1225 885 860 1350 1215 945 915 1775 1725 1545 1500 2020 1960 1450 1405 1970 1770 1425...

Страница 26: ...Amps BTUH Amps BTUH Amps BTUH 4 16 7 13650 14 4 10240 5 20 8 17065 18 1 12800 6 14 4 20500 12 5 15360 7 2 20500 8 33 3 27300 28 8 20475 9 21 7 30600 18 7 23030 10 8 30700 10 41 6 34130 36 2 25600 12...

Страница 27: ...8 X X EHWA03 A10 X X EHWA03 A15 X X EHWA03 B06 X EHW36A B06 X EHWA03 B09 X X EHWA37 B15 X X EHWC03A C06 X X EHWC03A C09 X X EHWA03A C12 X X EHWA03A C15 X X EHWA05 A05 X X EHWA05 A10 X X X X EHWA05 A15...

Страница 28: ...WA03 A05L X X EHWA03 A08L X EHWA03 A10L X X EHWA03 A15L X X EHWA03 B09L X X EHWA37 B15L X X EHWC03 C09L X X EHWA03 C15L X X EHWA05 A05L X X X EHWA05 A10L X X X X EHWA05 A15L X X X X EHWA05 B09L X X EH...

Страница 29: ...Bldg Equipment Enthalpy Economizer Bldg Equipment DB Temp X X X BFAD 3 Barometric Fresh Air Damper Standard X ECONWMS E3 ECONWMT E3 ECONWMT T3 Economizer School Version Enthalpy Economizer Bldg Equipm...

Отзывы: