Solair J AB Series Скачать руководство пользователя страница 21

Manual 2100-707D 

Page 

21 of 39

However, three phase compressors will rotate in either 
direction depending upon phasing of the power.  
Since there is a 50-50 chance of connecting power 
in such a way as to cause rotation in the reverse 
direction, verification of proper rotation must be made. 
Verification of proper rotation direction is made by 
observing that suction pressure drops and discharge 
pressure rises when the compressor is energized. 
Reverse rotation also results in an elevated sound level 
over that with correct rotation, as well as substantially 
reduced current draw compared to tabulated values.
Verification of 

proper rotation

 must be made at the time 

the equipment is put into service. If improper rotation 
is corrected at this time, there will be no negative 
impact on the durability of the compressor. However, 
reverse operation for over 1 hour may have a negative 
impact on the bearing due to oil pump out.

NOTE:

  If compressor is allowed to run in reverse 

rotation for an extended period of time, the 

compressor’s internal protector will trip.

All three phase compressors are wired identically 
internally. As a result, once the correct phasing is 
determined for a specific system or installation, 
connecting properly phased power leads to the same 
Fusite terminal should maintain proper rotation 
direction.
The direction of rotation of the compressor may be 
changed by reversing any two line connections to the 
unit.

Phase Monitor

All units with three phase scroll compressors are 
equipped with a three phase line monitor to prevent 
compressor damage due to phase reversal.
The phase monitor in this unit is equipped with two 
LEDs. If the Y signal (call for cooling) is present at the 
phase monitor and phases are correct, the green LED 
will light.
If phases are reversed, the red fault LED will be lit and 
compressor operation is inhibited.
If a fault condition occurs, reverse two of the supply 
leads to the unit. 

Do not reverse any of the unit factory 

wires as damage may occur.

Condenser Fan Operation

NOTE:

  Certain models may be equipped with a low 

ambient control (LAC), and if so, the condenser fan 

motor will have a delayed start until system refrigerant 

operating pressure builds up. After starting, the fan 

motor may or may not cycle depending upon ambient 

conditions. This is normal operation.

Service Hints

1.  Caution owner/operator to maintain clean air filters 

at all times and also not to needlessly close off 

supply and return air registers. This reduces airflow 
through the system, which shortens equipment 
service life as well as increasing operating costs.

2.  Check all power fuses or circuit breakers to be sure 

they are the correct rating.

3.  Periodic cleaning of the outdoor coil to permit full 

and unrestricted airflow circulation is essential

.

Sequence of Operation

Circuit R-Y1 makes at thermostat pulling in compressor 
contactor, starting the compressor and outdoor motor. 
(See 

NOTE

 under 

CONDENSER FAN OPERATION

 

concerning models equipped with low ambient control.) 
The G (indoor motor) circuit is automatically completed 
by the thermostat on any call for cooling operation or 
can be energized by manual fan switch on subbase for 
constant air circulation. On a call for heating, circuit 
R-W1 makes at the thermostat pulling in heat contactor 
for the strip heat and blower operation. On a call for 
second stage heat, R-W2 makes bringing on second 
heat contactor, if so equipped.

Balanced Climate

TM

 Mode

Balanced Climate™ is a great comfort feature that can 
easily be applied under any normal circumstances. If 
the air conditioning system is being set up in a typical 
environment where 72°F is the lowest cooling setpoint, 
remove the Y1/Y2 jumper and install a 2-stage cooling 
thermostat. This will increase the humidity removal 
up to 35% and provide a much more comfortable 
environment.

If the application is likely to require air conditioning 

operation below 60°F outdoor conditions, a low 

ambient control (LAC) kit must be installed.

 The LAC 

kit is equipped with an outdoor temperature switch 
that disables Balanced Climate mode when the outdoor 
temperature drops below 50°F. This prevents potential 
evaporator coil freeze up issues. The LAC kit also 
comes with an evaporator freeze protection thermostat 
that cuts out the compressor if the evaporator begins to 
freeze up.

If the unit is being installed with any ventilation 

package, an LAC kit must be installed.

 Failure to utilize 

an LAC with any air conditioner can cause coil freeze 
up.
Balanced Climate can readily be applied to duct-free 
(supply and return air grille) applications. It may also 
be applied to ducted applications with 

limited static 

of 0.20" ESP (total including both supply and return 

statics)

. Consult Bard Application Engineering for 

details prior to implementation.

CAUTION:

 

Balanced Climate is not a replacement for 

a dehumidification (hot gas reheat) unit for extreme 

applications, but rather an enhancement feature for 

limited climates and applications.

Содержание J AB Series

Страница 1: ...ioner Models INSTALLATION INSTRUCTIONS J18AB A J24AB A J24AB B J24AB C J30AB A J30AB B J30AB C J36AB A J36AB B J36AB C Manual 2100 707D Supersedes 2100 707C Date 2 3 21 J18LB A J24LB A J24LB B J30LB A...

Страница 2: ...on Make Timer 22 Short Cycle Delay on Break 22 Low Pressure Detection 23 High Pressure Detection 23 Test Mode 23 Brownout Protection with Adjustment 23 Pressure Service Ports 23 Service 24 Troublesho...

Страница 3: ...ne 212 642 4900 Fax 212 302 1286 ASHRAE American Society of Heating Refrigeration and Air Conditioning Engineers Inc 1791 Tullie Circle N E Atlanta GA 30329 2305 Telephone 404 636 8400 Fax 404 321 547...

Страница 4: ...unit These instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Not...

Страница 5: ...metallic return air grille is required with installations not requiring a return air duct The spacing between louvers on the grille shall not be larger than 5 8 Any grille that meets with 5 8 louver c...

Страница 6: ...hinder unit installation and servicing including outdoor electrical conduits junction boxes wall drains vent hoods windows doors overhangs and posts Condensate Water Drainage Review all codes and requ...

Страница 7: ...ructure through ventilation options including fresh air dampers ventilators economizers and energy recovery ventilators Be sure to install the return grille with the louvers pointed downward towards t...

Страница 8: ...ark bolt hole locations and bottom mounting bracket location Install bottom mounting bracket with field supplied fasteners to wall if it is to be used optional Bracket must be level and installed in t...

Страница 9: ...unit and J A right side compressor and controls for right unit See Specifications Sheet S3582 TABLE 1 Clearance Required for Service Access and Adequate Condenser Airflow Model Left Side Right Side D...

Страница 10: ...lectrical Entrances Side Wall Supply Air Opening Shipping Location Brackets Return Air Opening Built In Mounting Top Rain Flashing Bottom Installation Bracket Back View 44 O E R S S S S S T N B P M L...

Страница 11: ...and Hole Location View Right Side View TOP FLASHING AT TIME OF INSTALLATION OPENING MIS 3157 A ENTIRE LENGTH OF TOP TOP NOTES OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE WALL HEATER ACCESS RA...

Страница 12: ...NOTES 1 4 CLEARANCE ON ALL HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICONE CAULKING BE PLACED BEHIND IS ON OPPOSITE LEFT SIDE OPENING CONTROLS AND HEAT...

Страница 13: ...SECTION VIEW OF SUPPLY AIR DUCT FOR WALL MOUNTED UNIT SHOWING 1 4 CLEARANCE TO COMBUSTIBLE SURFACES Fire hazard Maintain minimum 1 4 clearance between the supply air duct and combustible materials in...

Страница 14: ...CTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTU...

Страница 15: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Страница 16: ...or airflow amount and extending the run time to help extract more humidity during cooling operation In heating mode the reduced airflow provides a warmer supply air temperature creating more comfortab...

Страница 17: ...ration cycles the condenser fan on off to maintain desired liquid pressure while modulating LAC operation is factory adjusted and slows the condenser fan speed rpm Outdoor Temperature Switch and Freez...

Страница 18: ...6 B 4 5 7 If not equipped with a ventilation option to plug in a jumper plug must be installed 4 2 8 9 TABLE 6 Wall Thermostats Part Number Predominate Features 8403 060 1120 445 3 stage Cool 3 stage...

Страница 19: ...ntrol Optional for ECON Only See vent installation manual 6 For vent operation add jumper if optional CO2 controller is not used Vent will run while blower is energized For ECON CRV V an additional wi...

Страница 20: ...refrigerant it must come out of the charging cylinder tank as a liquid to avoid any fractionation and to ensure optimal system performance Refer to instructions for the cylinder that is being utilized...

Страница 21: ...filters at all times and also not to needlessly close off supply and return air registers This reduces airflow through the system which shortens equipment service life as well as increasing operating...

Страница 22: ...ied with a factory installed vent package it will be plugged in but the jumper plug will also be tethered next to the connection for troubleshooting purposes if necessary Compressor Control Module The...

Страница 23: ...mers can be set by DIP switches in order to delay signaling a power brownout for a specific length of time after compressor contactor is energized This allows the compressor a time period to start eve...

Страница 24: ...3302 PA13362 A B PA13422 A B C PA13482 A B C PA13602 A B C contain the X13 Series Motors TROUBLESHOOTING GE X13 SERIES ECM2 3 MOTORS If the Motor is Running 1 It is normal for the motor to rock back a...

Страница 25: ...utput 24VAC Common 24VAC Common 24VAC R Signal through thermostat output 2 If the motor has proper high voltage and ground at the L L1 G N L2 connections then continue with the Model SelecTech Communi...

Страница 26: ...unit to the serial plate charge Removal of Fan Shroud 1 Disconnect all power to the unit 2 Remove the screws holding both grilles one on each side of unit and remove grilles 3 Remove nine screws hold...

Страница 27: ...de High Side 132 315 136 337 140 361 143 386 146 412 148 439 151 467 153 495 154 525 156 556 157 587 159 626 J24A L 75 62 Low Side High Side 123 302 125 323 127 344 129 367 132 391 134 415 136 441 137...

Страница 28: ...138 409 140 436 143 463 145 492 147 522 149 552 151 584 154 623 W24A L 75 62 Low Side High Side 116 296 118 318 120 339 122 362 123 385 125 410 128 434 130 460 132 488 135 515 137 544 139 579 80 67 Lo...

Страница 29: ...3 51 25 25 35 60 10 10 8 6 10 10 10 10 J36AB C00 C0Z C06 C09 C15 460 3 1 1 1 1 11 12 17 26 15 15 20 30 14 14 14 12 14 14 14 12 These Minimum Circuit Ampacity values are to be used for sizing the field...

Страница 30: ...460 3 1 1 1 9 15 24 15 15 25 14 14 10 14 14 10 These Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electrical code latest version Article 3...

Страница 31: ...black wire on the blower speed terminal block to either MED or HI Refer to Table 14 on page 33 for the corresponding airflow of each tap Set the unit duct static based on the highest airflow that the...

Страница 32: ...s used when Balanced Climate is called for by energizing the Y1 terminal of the low voltage terminal block with 24VAC Speed tap 2 is overridden if taps 3 4 or 5 are energized Speed Tap 3 Default LO Co...

Страница 33: ...770 755 910 885 955 930 0 25 740 730 890 865 935 910 0 30 715 705 870 840 915 885 0 40 670 650 825 805 870 845 0 50 630 585 785 765 825 805 J30AB J30LB 0 00 830 825 1050 1020 1170 1135 1200 1205 0 10...

Страница 34: ...igh Low A0Z A05 A08 A10 A15 50 50 50 30 50 50 50 40 40 50 50 50 35 35 B0Z B06 B09 B15 50 40 50 50 50 35 50 40 50 30 C0Z C06 C09 C15 50 50 50 50 50 45 50 50 40 35 TABLE 16 Electric Heat Models 240V 1 2...

Страница 35: ...cription CMC 15 Start Kit 230V 1 Phase X X FAD NE2 Fresh Air Damper No Exhaust X ECONS 3 Economizer School X ECONWD 2 Economizer Bldg Equipment Enthalpy or Temperature X FAD NE3 Fresh Air Damper No Ex...

Страница 36: ...HW2TAB A08 X EHW2TA A10 X X EHW2TA B06 X EHWH24B C06 X EHW3TA A05 X X EHW3TA A08 X X EHW3TA A10 X EHW3TAB A10 X EHW3TA A15 X EHW3TAB A15 X EHW30A B06 X EHW3TA B06 X EHW3TA B09 X EHW3TAB B09 X EHW3TA B...

Страница 37: ...1TAB A08L X EHW2TAB A05L X EHW2TAB A08L X EHW2TA A10L X X EHW2TA B06L X EHW3TA A05L X X EHW3TA A08L X EHW3TA A10L X EHW3TAB A10L X EHW3TA A15L X X EHW3TA B09L X EHW3TAB B09L X EHW3TA B15L X EHW3TAB B1...

Страница 38: ...Manual 2100 707D Page 38 of 39 GRAPH 1 J18 B FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 2 J24 B FAD NE2 3 W O Exhaust Ventilation Delivery...

Страница 39: ...Manual 2100 707D Page 39 of 39 GRAPH 3 J30 B FAD NE2 3 W O Exhaust Ventilation Delivery GRAPH 4 J36 B FAD NE2 3 W O Exhaust Ventilation Delivery...

Отзывы: