The Answer in
Power Protection
SOLA 610 UPS Installation
Your UPS should be in a controlled environment. A controlled
environment is one that is indoor, temperature-controlled and free of
conductive or semi-conductive contaminants.
The SOLA 610 is
intended for indoor use only.
There should be adequate ventilation and
the location should be free of dust and fumes. Do not install the unit next
to open windows where uncontrolled environmental conditions could
affect the unit. Do not install the unit in any type of enclosure without first
calling SOLA Technical Support. The unit must have unrestricted air flow.
CAUTION
The environmental specifications shown in Table 1
(below) show the temperature and humidity limits of
the UPS. Do not exceed these limits.
2.6 UPS Locations
ENVIRONMENTAL SPECIFICATIONS
Ambient Operating
< 1500 m
0
o
C to 40
o
C (32
o
F to 104
o
F)
Temperature
1500 - 3000 m
10
o
C to 35
o
C
Ambient Storage
All Models:
-15
o
C to 40
o
C (5
o
F to 104
o
F)
Humidity
All Models:
20% to 95%, non condensing
Altitude
All Models:
8,000 feet (2500M) max.
To optimise the performance of your UPS we
recommend you ensure the battery is fully charged
before you use the UPS to support your critical load.
To recharge the battery, place the UPS close to a wall
outlet and connect the matching line cord to the UPS
receptacle then plug it into the wall socket. For units
that have hardwired connections, have your electrical
contractor install the UPS wiring.
When power is supplied to the UPS (without operating
any front panel switches), the UPS will go through a
short test sequence, and the cooling fan will start.
On the front panel the line indicator and the
bypass indicator will illuminate. At this time there
is power available at the output sockets.
Table 1
2.7 Recharging the UPS Battery
!
3