Maintenance
34
12.0 M
AINTENANCE
The S4K4U6000 requires very little maintenance. The batteries are valve-regulated, non-spillable,
flame retardant, lead acid and should be kept charged to obtain their design life. The UPS continu-
ously charges the batteries when connected to the utility supply.
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours
every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri-
odically will permanently degrade battery capacity.
The S4K4U6000 is designed to allow the user to safely replace the internal batteries. Read the safety
cautions before proceeding. Contact your local dealer or Sola/Hevi-Duty representative to obtain the
appropriate replacement battery kit part number and pricing.
12.1
Battery Replacement
12.1.1 Internal Battery Replacement Procedures
1. Gently remove the front metal bezel cover from
the UPS by pulling forward.
2. Loosen the two captive screws on the front
battery door. Lay the battery door aside for
reassembly.
3. Grasp the battery pack assembly and pull it out
of the front of the UPS. Be prepared to support
the weight of the battery as it is withdrawn.
4. Unpack the new battery assembly taking care
not to destroy the packing. Compare new and
old battery assemblies to make sure they are the
same. If so, proceed with
Step 6
; otherwise
STOP and contact your local dealer or Sola/
Hevi-Duty representative.
5. Line up and slide in the new replacement
battery pack.
6. Reattach the front battery door, tightening the
two captive screws finger tight.
7. Reattach the front plastic bezel to the UPS.
!
CAUTION
A battery can present a risk of electrical shock and high short circuit Current. The following
precautions should be observed before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact
your local dealer or Sola/Hevi-Duty representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
NOTE
These are hot-swappable replacement batteries. However, caution should be exercised because
during this procedure the load is unprotected from disturbances and power outages.
!
Liebert
!
!
!
+
-
12Vx12(144V)
9Ahi45W
WAR
NING:
ADVERTENCIA:
AVE
RTISSEMENT
:
Front Bezel
Battery Cover
Captive Screws
Battery
Battery Cover
UPS
Содержание S4K4U6000
Страница 1: ...POWER AVAILABILITY S4K4U6000 USER MANUAL 120 208V On Line UPS 120 208V 120 240V...
Страница 2: ......
Страница 50: ...Specifications 44...
Страница 51: ......