STV100K Series Instruction Manual • 9
4.0 Specifications
Table 2: Technical Specifications
Parameters
Model
STV100K-
10N
STV100K-
24L
STV100K-
10S
STV100K-
10Y
STV100K-
23Y
Nominal Input Voltage
120 V
240 V
120/208–240 V
120/208 V
230/400 V
System Configuration
1-phase
2W + G
1-phase
2W + G
1-phase
3W + G
3-phase wye
4W + G
3-phase wye
4W + G
Maximum Continuous
Operating Voltage
(MCOV)
125% of the nominal level for 120 V; 115% for all other voltages
Line Frequency
47–63 Hz
Response Time
<0.5 ns
A/C Rating
65 kAIC
Fusing
Thermal and fault current
Nominal Discharge
Current Rating
3 kA
Modes of Protection
All Modes: L–N, L–L, L–G, N–G
Operating Temperature
-40°C to +60°C (-40°F to +140°F)
Operating Humidity
0 to 95% non-condensing
Noise Attenuation
40 dBA maximum
Dimensions, W x D x H
6.00 in. x 4.00 in. x 3.20 in. (152.4 mm x 101.6 mm x 81.28 mm)
Net Weight
8.0 lb. (3.63 kg)
Enclosure
Metal, NEMA 12 enclosure
Connection/Mounting
Type
Parallel/Flange
Status Indication
Red and green LED status indicators, audible alarm, Form C contacts
Safety Approvals
UL 1449 3
rd
edition, cULus Listed
Warranty
10 years
UL 1449 3
rd
Edition, Type 2 Voltage Protection Ratings
Line to Neutral
600 V
N/A
600 V
600 V
1200 V
Line to Line
N/A
1000 V
1000 V
1000 V
2000 V
Line to Ground
700 V
1200 V
700 V
700 V
1200 V
Neutral to Ground
700 V
N/A
700 V
700 V
1200 V
High Leg to Neutral
N/A
N/A
N/A
N/A
N/A
High Leg to Line
N/A
N/A
N/A
N/A
N/A
High Leg to Ground
N/A
N/A
N/A
N/A
N/A
Peak Surge Current Capability
Per Phase
100 kA
100 kA
100 kA
100 kA
100 kA
Line to Neutral
50 kA
N/A
50 kA
50 kA
50 kA
Line to Line
N/A
50 kA
50 kA
50 kA
50 kA
Line to Ground
50 kA
50 kA
50 kA
50 kA
50 kA
Neutral to Ground
50 kA
N/A
50 kA
50 kA
50 kA