S4KC SEriES USEr mAnUAL |
43
11.
insert the replacement UPS power module.
12.
Slide the power module restraint lever back into the locked position.
NOTE:
The power module restraint lever must be fully engaged for the UPS to operate in normal mode.
13.
reconnect the slotted internal battery connectors.
14.
reconnect the external battery cables, if used.
15.
reattach both front cover grilles.
16.
reattach the front metal bezels.
17.
Close the input circuit breaker on the rear of the UPS (see Figure 7).
18.
Close the output circuit breaker on the rear of the UPS (see Figure 7).
19.
move the manual bypass breaker on the rear of the UPS back to the inVErTEr position (see Figure 7).
20.
Slide the bracket back next to the manual bypass breaker and tighten its captive screw.
21.
Press the On button on the front panel one time to return the UPS to normal mode operation (see Figure 24).