Uninterruptible Power Supplies
Table 16: Specifications
10 Bay (A)
16 Bay (B)
12 Bay (C)
16 Bay (D)
10 Bay (E)
16 Bay (F)
Xfmr-free
Xfmr-based
Xfmr-free dual inverter
Capacity
15 kVA
20 kVA
15 kVA
20 kVA
15 kVA
20 kVA
13.5 kW
18 kW
13.5 kW
18 kW
13.5 kW
18 kW
General and Environment
Conducted and radiated EMC levels
IEC/EN/AS 62040-2 Cat 2, CISPR22 Class A, FCC Part 15 Class A
Compliant immunity standards
IEC/EN/AS 61000-4-2, 3, 4, 5, 6
Environmental
WEEE and ROHS2 (6 by 6), REACH Compliant
ENERYGY STAR® qualified
Yes
All Models
Yes
All Models
Yes
10, 15, 20 kVA
Yes
10, 15, 20 kVA
Yes
All Models
Yes
All Models
Dimensions — mm (in) & Weight kg (lbs)
Width
440 mm (17 in)
440 mm (17 in)
440 mm (17 in)
440 mm (17 in)
440 mm (17 in)
440 mm (17 in)
Depth
800 mm (32 in)
850 mm (34 in)
800 mm (32 in)
850 mm (34 in)
800 mm (32 in)
850 mm (34 in)
Height
695 mm (27 in)
970 mm (38 in)
1060 mm (42 in)
1240 mm (49 in)
695 mm (27 in)
970 mm (38 in)
Weight (frame rating
populated)
Unit Weight
256 kg (565 lbs)
318 kg (700 lbs)
361 kg (795 lbs)
417 kg (920 lbs)
256 kg (565 lbs)
318 kg (700 lbs)
Shipping Weight
274 kg (605 lbs)
336 kg (740 lbs)
379 kg (835 lbs)
435 kg (960 lbs)
274 kg (605 lbs)
336 kg (740 lbs)
Environmental
Operating temperature
0 °C - 40 °C (32 °F - 104 °F)
Relative humidity
0 - 95%, non-condensing
Altitude
3000 m (10000 ft) @ 25°C (77°F)
Efficiency (AC-AC)
91.8-92.0%
91.6-92.0%
88.5-89.9%
88.6-89.7%
90.4-91.0%
90.0-91.0%
Heat dissipation
4208 BTU / Hr
5747 BTU / Hr
5528 BTU / Hr
7965 BTU / Hr
4904 BTU / Hr
6768 BTU / Hr
Input Data
Nominal input voltage
200/208/220/230/240 Vac; Single Phase
200/100, 208/120, 220/110,
230/115, 240/120 Vac;
Single Phase
380/400/415 Vac; 3 Phase
Not Applicable
Input Voltage Range
The input voltage range based on the ouput loading, refer to User Manual
Power Factor
Single-phase input, > 0.99 Cos;
three-phase input, > 0.95 Cos
Single-phase input, > 0.99 Cos
Input Frequency Range
40 Hz to 70 Hz auto-sensing
Battery Module
Battery capacity
36W @ 15min-rate to 1.67V per cell @ 25°C (77°F)
Battery Back-up Time (full load)
5 minutes (for non-redundant system which has equal number of battery strings and power modules)
Maximum Charge current (full load)
Power module internal charger: 1.8A / Charger module: 10A
Nominal Voltage
144 VDC
Recharge time
< 5 hours to 90% capacity (PM internal charger with 1:1 ratio of PM to Battery Strings)
Output Data
Output voltage
200/208/220/230/240 Vac; Single
Phase
100/100/173/200,110/110/
190/220, 115/115/199/230,
120/120/208/240 Vac; Single Phase
200/100, 208/120, 220/110,
230/115, 240/120 Vac; Single Phase
Voltage regulation
±3%
Voltage stability (100% step load)
±7%
Voltage Recovery time
≤
60 minutes
Voltage distortion
≤
3%, linear load
≤
5%, non-linear load
≤
7%, non-linear load
≤
5%, non-linear load
Output frequency
50/60 Hz
Output overload capability
< 104% continuous
105% - 130% for 1 min
131% - 150% for 10 sec
151% - 200% for 1 sec
> 201% for 250 msec