October 26
th
, 2022 35
Install Tips
Off-Grid Install Tips
Sol-Ark 8K will automatically operate in Off-Grid Mode without the grid (under the same power priority as TOU).
A.
Limiter Sensors are not required for completely Off-Grid installs unless using
Grid Peak Shaving with a Gen connected to Grid input breaker.
B.
The Grid input breaker on the Sol-Ark should be used as the Generator input
(4-30kW generators) so that you maintain Smart Load output capability
when off-grid. Smart Load will allow you to run high-power non-essential
appliances (hot water, dehumidifier, heat pump, irrigation pump) on solar
power instead of batteries. Therefore, you will use Grid Charge (default) in
the Battery Setup/Charge menu.
C.
When off-grid, there is no need for a transfer switch: connect the load output of the Sol-Ark to the whole home.
D.
Do not use Grid Sell or Limited To Home Modes Off-Grid. Only Limited power to load (default).
E.
The Auto Generator start functions as a 2-wire switch (closes the circuit when needing charging)
i.
Auto Gen-start will be triggered when the battery voltage or percent
reaches the level programmed in the battery setup menu. Then, the
generator will continue to charge the batteries until they are about
95% full (this percentage is not programmable) before turning the
generator off.
ii.
When using the Sol-Ark to control a generator, an exercise function
will turn on the generator once a week on Monday mornings at 8 AM
by default
F.
We recommend changing the "Grid Reconnect Time" under the Sell control
tab of the grid setup menu to 30 seconds; otherwise, the Sol-Ark will not charge from the generator until it has been
on for at least 5 minutes per the default value of 300 seconds.
G.
Under setup for Grid/Sell Control, select General Standard and "GEN connect to Grid Input." Then go to Grid input to
widen the input frequency range to 55-65Hz to work with any frequency generator.
H.
If you would like to use a wind turbine in conjunction with the Sol-Ark 8K,
the turbine must have a 48V charge controller with a dump load to prevent
overcharging the batteries. Connect the charge controller on the turbine to
the battery bank the Sol-Ark is using, and the turbine will help charge the
batteries.
I.
Don't forget to set the Battery capacity and reasonable charge rates.
Grid-Tie / No Battery Install Tips
A.
Under Battery setup, select no Battery & disable Activate Battery (or
system will beep).
B.
Note: a whole system power cycle is required when changing the battery to
no battery settings.
C.
Under Grid Setup, select Grid Sell.
D.
Touch Battery Icon to see the Detailed Volts View to verify your inputs &
outputs.
Содержание 8K-2P-N
Страница 5: ...October 26th 2022 5 Spec Sheet ...
Страница 9: ...October 26th 2022 9 Diagram 2 Diagram 3 ...
Страница 10: ...October 26th 2022 10 Note PV fuses are only required for 2 strings per MPPT Diagram 4 ...
Страница 12: ...October 26th 2022 12 GUI Screens Main Menus Basic Setup ...
Страница 13: ...October 26th 2022 13 c Battery Setup Grid Setup ...