6
WIRING
The SWH-4000 model has ten terminals as noted in Table 2. When
attaching wires to the connector, strip off only the minimum insulation
required (approx. 1/8'') and push the wire into the connector until the
insulation is flush or inside the connector body. This is particularly critical
for outdoor readers. While the reader itself is designed and protected to
IP65 standards, the cable wires can potentially corrode and short together if
not carefully mounted and tightly fastened in the connector body.
Table 3 indicates maximum wiring distances per Wiegand standard with
the three most common gauges of cable.
TABLE 2.
Connector Pins for Model SWH-4000
Pin
Description
Pin
1
External Beeper Control
6
Reserved for Future Use
2
Ground
7
External Green LED Control
3
Power (8 to 16 VDC)
8
External Red LED Control
4
D1 Wiegand
9
A - RS-485 – used for Flash upgrade
5
D0 Wiegand
10
B - RS-485 – used for Flash upgrade
TABLE 3.
Maximum cable distance for 18, 20, or 22 AWG wire
Wire Gauge
18 AWG
20AWG
22 AWG
Cable
Distance
500 feet
(152 meters)
300 feet
(91 meters)
200 feet
(61 meters)