20 • Control Keypad
________________________________________________________________________________________________
6.9.2
I/O Parameters settings – page 2
I/O PARAMETERS
***SETTINGS***
Display and default
values
Range Description
CONFIG. INPUT A
TEST INSUL. N.O.
EXT FAULT 3 N.C.
EXT FAULT 3 N.O.
EXT FAULT 2 N.C.
EXT FAULT 2 N.O.
EXT FAULT 1 N.C.
EXT FAULT 1 N.O.
EMERGENCY
RESTART
AUTHORIZED KEY
REMOTE RESET
TEST LINE
TEST INSUL. N.C.
TEST INSUL. N.O.
Sets MIP-6 INPUT A.
EXT FAULT 3 N.C.
(1)
is programmed for open to trip.
EXT FAULT 3 N.O.
(1)
is programmed for close to trip.
EXT FAULT 2 N.C.
(1)
is programmed for open to trip.
EXT FAULT 2 N.O.
(1)
is programmed for close to trip.
EXT FAULT 1 N.C.
(1)
is programmed for open to trip.
EXT FAULT 1 N.O.
(1)
is programmed for close to trip.
EMERGENCY RESTART
is
programmed to reset and
prevent insulation trip by the MIP-6. (See also PARAM.
SETTING below)
AUTHORIZED KEY
is programmed to prevent
parameter modifications. Closing the contact will
enable programming the MIP-6.
REMOTE RESET
is programmed to remote reset the
MIP-6. To remote reset close contact momentarily.
TEST LINE
is programmed to start the wiring test of the
cable from the resistor unit (RU7/RU13). Close the
contact to start the insulation measurement.
Applicable only in medium voltage applications.
TEST INSUL. N.C.
is programmed to start the
insulation measurement. Open the contact to start the
insulation measurement.
TEST INSUL. N.O.
is programmed to start the
insulation measurement. Close the contact to start the
insulation measurement
Note:
(1)
In order to be activated, this parameter must be
programmed to:
I/O PARAMETERS SETTINGS – Parameters CONFIG.
OUTPUT X (Refer to section
details)
TRIPPING/ALARM OPTIONS (Refer to section
page 23 for more details)
CONFIG. INPUT B
TEST LINE
Same as for CONFIG.
INPUT A.
CONFIG. INPUT C
REMOTE RESET
Same as for CONFIG.
INPUT A.
CONFIG. INPUT D
AUTHORIZED KEY
Same as for CONFIG.
INPUT A.
CONFIG. INPUT E
EXT FAULT 1 N.O.
Same as for CONFIG.
INPUT A.
CONFIG. INPUT F
EXT FAULT 2 N.O.
Same as for CONFIG.
INPUT A.
PARAM. SETTINGS
NOT LOCKED
LOCKED OUT
NOT LOCKED
When set to LOCKED OUT, AUTHORIZED KEY
programming in CONFIG INPUT A (See above)
functions normally.