no practical sense to aggregate the data.

Each module has its table of read watermeters, where there are IDs (serial numbers) of meters that should be
read by the module. If there are other watermeters in the reach, their messages are ignored. The module supports
receiving and transmitting of messages either in open mode, or in

encrypted mode

. The module allows forwarding

of original

alarm statuses

(”flags”) from watermeters together with normal readings, or conversion of ”flags” into

the

wacoSystem

alarm messages, that are sent immediately.

Content of INFO-messages is configurable. The messages contain identification and current statuses of module
parameters (uptime, battery voltage, processor temperature..), list of read watermeters, timestamps of reading
periods, and counter values of all watermeters in each reading period (including alarm flags). As

up to 110

readings

can be transmitted within one communication session, one message can contain results from up to 5

measurement intervals even in case of reading maximum number of 20 water meters.

The messages with aggregate data are handed over to the application server with using of NB-IoT service of GSM
provider. The data are transferred in form of standard IP/UDP packets, that are routed to the server of remote
reading application operator through the designated Access Point of GSM provider. Application server receives the
messages and performs their decoding, storing and further processing.

The NB-K868 module supports

bi-directional communication

and it is able to receive through the network

messages of ”SET” type, generated by remote computer.

These messages can be used for setting of module

parameters from the remote server.

1.3

Hardware features and power supplying

The module is enclosed in humidity-proof plastic casing with IP65 degree of protection and can be used in interiors
as well as in exteriors. The casing is designed for mounting on the wall or other construction element (beam,
pipe...). Module can be treated with an additional sealing by high-adhesion silicon filling, that can ensure proof
against inundation by water (IP68 grade). If this treatment is required from the manufacturer, it must be ordered
separately.

The module is power supplied by internal battery with up to 6 years lifetime for measurement frequency of 2
hours and broadcasting interval of 8 hours. One message can contain up to 110 readings. Battery lifetime can be
negatively influenced by shorter broadcasting period, or by storing and operation in sites with the temperatures
exceeding the recommended range.

The module is equipped with a SIM-holder for ”Micro-SIM” (3FF) format of SIM-card (15 x 12 x 0,76 mm). SIM-
holder is placed inside the module on the PCB. The module can be ordered with embedded SIM (eSIM) of chosen
GSM operator.

The module can be controlled and configured either by configuration cable, or wirelessly, by infra-red optical
converter. The module is equipped with the special circular aperture (”peephole”) for magnetic fixing of the optical
converter. The module can be also configured remotely, with using of back channel of bi-directional communication.

External appearance of the NB-K868 module is shown in the figure

1

.

Figure 1: View of the NB-K868 module

NB-K868

2

Содержание NB-K868

Страница 1: ...WIRELESS COMMUNICATION SYSTEM NB IoT NB K868 Revision 1 0 SOFTLINK s r o Tomkova 409 278 01 Kralupy nad Vltavou Czech Republic Phone 420 315707111 e mail sales softlink cz www softlink cz...

Страница 2: ...odule data messages 25 3 5 1 Structure and types of data messages 25 3 5 2 Description of INFO message 26 3 5 3 Description of TRAP message 28 3 5 4 Encryption of messages 28 4 Operational conditions...

Страница 3: ...NB K868 module parameters 21 4 Basic forms of NB K868 module in SOFTLINK Configurator application 21 5 Setting the list of read devices 22 6 Preview of NEP coding table for coding of variables in WAC...

Страница 4: ...n standard enable providing of international services roaming Bi directional communication is carried by standard Internet protocol with UDP transport layer Messages are transferred from the GSM opera...

Страница 5: ...t is able to receive through the network messages of SET type generated by remote computer These messages can be used for setting of module parameters from the remote server 1 3 Hardware features and...

Страница 6: ...Sensus iPERL Wireless M Bus Max number of read watermeters 20 Configuration interface RS232 Transmission speed 9600 Baud Operation mode asynchronous Transmission parameters 8 data bits 1 stop bit none...

Страница 7: ...ftlink cz en documents The description and meaning of all configuration parameters that can be checked and changed by cable can be found in the section 3 1 Setting of NB K868 parameters via configurat...

Страница 8: ...Configuration Timezone 1 Server IP 192 168 0 20 Ping IP 10 0 0 1 Server port 4242 Reply to server yes My src port 2000 APN Max session time 172800 sec 2d 0 00 00 Send periode 0 Hist periode 60 min Sen...

Страница 9: ...DIF VIF index 2 02 5b DIF VIF alarm 00 00 Alarms bit Burst 0 Leak 0 Baterry 0 Back flow 0 ID 1 76738783 DIF VIF index 3 00 00 DIF VIF index 4 02 5b DIF VIF alarm 00 00 Alarms bit 868Mhz modem No sent...

Страница 10: ...dow in sec recvsec Modem receive on sec radar show radar clradar clear radar hdata show history data sicap Set or get xtal capacity correction sixtal Set or get xtal frequence cfreq Set xtal from anal...

Страница 11: ...rom last reset info setting of individual module description The command reset performs the module reset After each reset the system starts with the parameters that are stored in FLASH memory If the c...

Страница 12: ...nfiguration At the start of the system the module copies saved configuration to operating configuration with which continues to work If the user changes configuration parameters it does so only in ope...

Страница 13: ...ng sicap frequency crystal capacity correction setting cfreq frequency constant correction setting It is strongly recommended not to use these commands during common operation 3 1 5 Commands for setti...

Страница 14: ...modem into the RADAR mode for 60 seconds mon recvsec 60 Modem goes to receive for 60 sec mon By using of the recvwin time command the length of receiving window parameter can be preset to the specifi...

Страница 15: ...delay energy consumption and service price To minimize information delays it is necessary to broadcast as often as possible On the other hand to minimize energy consumption it is advantageous to broa...

Страница 16: ...only SID meter ID and Alarm Alarm Flag values without RSSI value This setting will determine message content as it is described in detail in paragraph 3 5 The NB K868 module data messages Values of wa...

Страница 17: ...alarm variable alrb index type value assigning the alarm type to the alarm flag value The command WMBUS encryption key is used for setting of the encryption key for decryption of messages from indivi...

Страница 18: ...if the readout device is not a watermeter the DIF VIF value must be changed according to the actual designation in the message Return to the default setting can be done by entering of 00 00 value If i...

Страница 19: ...m bits 0 Burst 2 Leak 1 Baterry 4 Back flow 3 1 Burst 2 Leak 1 Baterry 4 Back flow 3 2 Burst 1 Leak 2 Baterry 3 Back flow 0 3 Burst 1 Leak 2 Baterry 3 Back flow 0 4 Burst 0 Leak 0 Baterry 0 Back flow...

Страница 20: ...The value of the param eter is factory preset to 60 minutes Current value can be checked by periode command without parameter Broadcasting period can be changed by entering of required number of minu...

Страница 21: ...tting of target server and communication gateway displays in the configuration summary as follows Server IP 92 89 162 105 Server port 2000 My src port 2000 APN cms softlink The My src port value is a...

Страница 22: ...bed parameters sess and tconn have significant influence on the energy consumption and battery lifetime If as an example the module sets up connection before each broadcasting it increases broad casti...

Страница 23: ...No sent 3 msg s No recv 0 msg s Modem state 4 ready Session count 1 Session timeout 172664 sec 1d 23 57 44 Modem IMEI 867724031580613 SIM CCID 89882390000036330010 SIM IMSI 901288001028645 Last RSSI 7...

Страница 24: ...le with the list of parameters of the NB K868 module is shown in the figure 3 Figure 3 Table of list of NB K868 module parameters Most of module parameters can be configured also by using of BT IRDA c...

Страница 25: ...setting can be made by editing the individual windows of the SENSORS table in the lower part of the WMBUS SENSUS SENSORS form The device can operate either only in the mode for receiving messages from...

Страница 26: ...channel can be used for setting of same parameters that can be set by optical interface because both systems work on the same principle More details about the back channel communication can be obtaine...

Страница 27: ...urr status No of sent messages from reset read only 19 No recv curr status No of received messages from reset read only 20 Modem state curr status internal GSM module status read only 21 Session count...

Страница 28: ...d jointly with order number of the variable called Index NEP coding table is centrally maintained by SOFTLINK and it is available on the public WEB address NEP Page Preview of NEP coding table for cod...

Страница 29: ...ferred only once at the beginning of variable part of the message Here there is a set of OID 205 x variables that forms a list of watermeters read by the module with their indexes Sets of historical r...

Страница 30: ...Input value 1 Current status of watermeter 1 1999 201 1 RF RSSI 1 Last message RSSI of watermeter 1 65 100 2 Input value 2 Current status of watermeter 2 12893 201 2 RF RSSI 2 Last message RSSI of wa...

Страница 31: ...s that are the same as in INFO message The only difference is that Message type OID 63 is set to 5 value what is a flag of TRAP type of message After this part of the message there is always Alarm cod...

Страница 32: ...ge number 19 Encrypted block Encrypted part of the message rest of variables In the encrypted part of message there are all other variables encrypted by block cipher The first variable in the encrypte...

Страница 33: ...nstallation It is recommended to lead antenna and signal cables as far from 230 50 Hz power cables as possible 4 1 2 Risk of premature battery discharge The devices are equipped with the long duration...

Страница 34: ...l battery it is recommended to keep the long transmitting period configured until the module s installation As NB IoT services are charged by GSM operator it is recommended to insert SIM and activate...

Страница 35: ...range The appearance of the printed circuit board may vary slightly depending on the modification of the module Figure 8 Detail of NB K868 module PCB The case of NB K868 module consists of two parts h...

Страница 36: ...tch is on the open side of the case i e on the side where the lid is screwed on The sealing nut of the cable gland must be fully loosened so that the antenna or antenna cable can easily slide out of t...

Страница 37: ...by the module due to the meter failure expired metrology period or for any other reason follow this procedure do not open the module if not really necessary Rewrite ID serial number of original meter...

Страница 38: ...s of signal and the level of risk of module mechanical damage It is necessary to carry out the installation carefully with using of high quality mounting components To prevent an unexpected breakdown...

Страница 39: ...ccasional interference jamming of radio signal from external source another radio system in the same frequency band or industrial disturbance low level of transmitting signal caused by transmitter fai...

Страница 40: ...ssages from watermeters as described in paragraph 5 1 4 Failures of communication with watermeters 2 Readings from some of watermeters read by the module are not available In this case it is recommend...

Страница 41: ...68 WACO or WB169 Wireless M BUS series of modules can be found on the manufacturer website www wacosystem com www softlink cz If interested in any additional information related to application of radi...

Отзывы: