BC-600-PB
Display and Control in Stand-Alone Mode
Softing
Page 33
8.3.1.4
Station status
This function displays the station status for each bus station, i.e. for all masters
and all slaves.
Fig. 24: Live Status with station status of a master
Fig. 25: Live Status with station status of a slave
The PROFIBUS address of the bus station is displayed right after “DP#” on the
left of line 1. The letter in the middle indicates whether the device is a master
(M) or slave (S). If the letter is enclosed in square brackets, the BC-600-PB
was able to determine the address of the PROFIBUS device to which it is
connected. In the above example, the test tool is connected to the device with
the address 11 (see
Fehler! Verweisquelle konnte nicht gefunden
werden.
). On the right, you see the live list changes (see page
) for this bus
station.
Line 2 shows the number of retries on the left, and the worst quality index of
this bus station on the right.
Line 3 indicates the number of diagnostics on the left, and the best quality
index of this bus station on the right.
Note: The update rate for the live status substantially depends on the number
of bus stations and the signal quality.