Technical data
6.1
Specifications
Power supply
18 VDC...32 VDC; SELV/PELV supply mandatory
Typical input current: 200 mA, maximum input current: 1 A
(allowing for rush-in current at switch-on).
No power supply to PROFIBUS PA segments through mbGate PA.
Ethernet
IEEE 802.3 100BASE-TX/10BASE-T
Minimum ambient
operating
temperature
-40 °C (see
for the maximum ambient
temperature depending on the mounting position)
Storage temperature
-40
°C...+85
°C
Altitude
Must not exceed 2,000 m
Location
Indoor use only; no direct sunlight
Safety standard
IEC/EN/UL 61010-1 Safety requirements for electrical equipment for
measurement, control and laboratory use - Part 1: General
requirements
IEC/EN/UL 61010-2-201 Safety requirements for electrical
equipment for measurement, control and laboratory use - Part 2-
201: Particular requirements for control equipment.