FG-200 HSE/FF Modbus - Qui ck Sta rtup Gui de
34
© Softing Industrial Automation GmbH
6.2
Installation positions
The gateway FG-200 can be mounted horizontally and vertically. Depending on the
installation position, different ambient operating temperatures (Ta) are allowed:
Minimum distance
Provide a minimum distance of 50 mm to the air inlet and air outlet to ensure
natural convection.
Rotated installation position
The maximum permissible ambient temperature values also apply to a 180°
rotated installation position.
Horizontal installation position
Maximum number
of fieldbus channels
Maximum fieldbus
voltage
Minimum
distance
Maximum permissible
ambient temperature Ta
4
32 VDC
0 mm
55 °C
2
24 VDC
0 mm
60 °C
4
32 VDC
17.5 mm
65 °C
2
24 VDC
17.5 mm
70 °C