Softing CAN-AC 104 Series Скачать руководство пользователя страница 3

 

Page: 3 

Table 1: I/O address selection (1=ON, 0=OFF) 

DIP switch (S2) 

I/O Range

(hex) 

1 2 3 4 5 6 7 8 

 

0 1 1 0 1 1 1 1  240-243 

 

0 1 1 0 1 1 1 0  244-247 

0 1 1 0 1 1 0 1  248-24B 

 

0 1 1 0 1 1 0 0  24C-24F 

0 1 0 1 1 1 1 1  280-283 

0 1 0 1 1 1 1 0  284-287 

0 1 0 1 1 1 0 1  288-28C 

0 1 0 1 1 1 0 0  28C-28F 

Table 2: I/O base address values (OFF)  

DIP 

switch 

Value (hex) 

200 

100 

80 

40 

20 

10 

PC/104-

connector

open

open

CAN-104 V1.00

S# xxxxxxx

S2

8

1

open

open

J1

16 pin

X10

16 pin

X13

D-SUB 9 or

interface adapter

CAN 2

D-SUB 9 or

interface adapter

CAN 1

DIP switch for

I/O address

setting

J9

 

1.4 Driver configuration 

CAN-ACx-104 needs to be added to the runtime configuration, by the following steps. 

 Click 

Start – All Programs – Softing CAN – Runtime System Configuration – Softing CAN 

Interface Manager

 

  Select the CAN-ACx-104 branch of the tree view at the left side and click 

Add. 

  Enter the information you are asked for and proceed with the 

Next

 button. 

  The board will then be added to the system configuration. 

  For more details on the driver configuration click 

 

Start – All Programs – Softing CAN – Runtime System Configuration – SCIM Manual

  

2  Pin Assignment  

The D-Sub 9 connectors are replaceably plugged into the PC/104 interface by a 16 pin 
ribbon cable connector (see Figure 1). They can be individually fixed at the housing of the 
PC as required by the customers system. The pinning of the D-Sub 9 connectors is defined 
according to the CiA recommendation for the CAN High Speed Bus The shield is connected 
to earth via the PC housing. 

Figure 1: CAN-ACx-104 layout 
scheme 

Отзывы: