SOFAR 3.3~12KTLX-G3
User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 27 -
SOFAR 5.5KTLX-G3 3~4, recommend 3
18~25
16A/230V/3P current leakage
protection 0.1A
SOFAR 6.6KTLX-G3 3~4, recommend 4
18~25
20A/230V/3P current leakage
protection 0.1A
SOFAR
8.8KTLX-G3-A
4~6, recommend 5
18~25
25A/230V/3P current leakage
protection 0.1A
SOFAR 8.8KTLX-G3 4~6, recommend 5
18~25
25A/230V/3P current leakage
protection 0.1A
SOFAR
10KTLX-G3-A
4~6, recommend 5
18~25
25A/230V/3P current leakage
protection 0.1A
SOFAR
11KTLX-G3-A
5~7, recommend 6
18~25
32A/230V/3P current leakage
protection 0.1A
SOFAR 11KTLX-G3 5~7, recommend 6
18~25
32A/230V/3P current leakage
protection 0.1A
SOFAR 12KTLX-G3 5~7, recommend 6
18~25
32A/230V/3P current leakage
protection 0.1A
Table 4- 2 AC breaker and RCD specifications
Figure 4- 5 Incorrect connection between load and inverter
The resistance at connection point must less than 2Ω. In case to have a properly
anti-islanding function, please choose the high-quality PV cable and ensure the
power loss is less than 1%. Meanwhile, the inverter AC side to grid connection
point must less than 100m. the relation between cable length, cross section area
and power loss as below: