 instalowane ty his  equipment  may  only  be  installed  by  a  qualified  technician  who  is  familiar 

with the  installation,  monitoring  and maintenance of this type of equipment, and uses suitable tools.

Mechanical

To ensure safe operation, the equipment must be firmly fixed.

The installation must prevent contact with the fan's impeller, through the use of grilles, accessories, or by installing

a connecting tube of a suitable length.

The  fan  should  be  installed  so  that  it  does  not  cause  vibration  in  the  ducts  or  building  and  to  facilitate  its

maintenance and cleaning.

The equipment must be installed in such a way that the whole of its surface area is adhered to the surface on
which it is installed.

Do not connect the elbows close to the equipment's connecting flanges or clamps

When connecting the ducts, ensure that the airflow direction is correct in accordance with the arrows indicating

flow direction through the equipment.

Once the mechanical assembly is complete, it is important to check that the impeller turns freely, with no friction or

tension.

Electrical

Check if the equipment is connected to the power source in accordance with the instructions on the cover of the

connection box.

Select a power cable with a suitable cross-section for the current used by the equipment.

IMPORTANT

: When the equipment is controlled by reducing the voltage, the motor's current may be higher than

the rated value.

Check if the electrical characteristics stated on the plate correspond to the power supply.

An  external  protective  component  must  be  connected  (a  relay,  magneto-thermal  protection  system  or  fuse),  in

accordance with current regulations.

The equipment's earth connection must be connected.

If the motor speed control is used, it must be guaranteed that the motor will operate correctly.

Start-up

After starting up the motor, it is important to check that the motor is turning correctly, without vibrations or unusual

noises.

A check must be made to ensure that the motor's actual power consumption does not exceed the level stated on

the equipment's label and that it does not heat up excessively.

The machine must not be switched on and off intermittently, as this could damage the winding of the motor or the

insulation, due to overheating.

7. Maintenance

Maintenance must be performed by qualified technicians.

The bearings are greased and sealed for life. Nevertheless, changing them about every 25.000 hours effective

running time is recommended and 20.000 hours for ATEX models.

If the fan is not equipped with an air filter, the only maintenance required is to clean the impeller; this must be

done at least once a year.

Care must be taken when cleaning the impeller, in order not to affect its balance.

It is not advisable to use chemical cleaners or aggressive substances, as they could damage the equipment.

If a part must be replaced, consult the distributor.

8. Disposal

Careless or negligent disposal of the equipment may cause contamination. The disposal process must be carried out in

compliance with the standards and regulations applicable in the country.

9. Warranty

Incorrect use of the equipment and failure to observe the instructions in this manual may result in the cancellation of the
warranty.

Содержание HT

Страница 1: ...Code 1134973 Doc Num 0000005524 2016 10 05 www sodeca com HT HT ATEX PL EN Dokumentacja techniczno ruchowa User Manual ...

Страница 2: ...Rys 1 Rys 2 Rys 3 HT 25 63 HT 71 100 HT 25 63 HT 25 63 ...

Страница 3: ...00 48 47 17 5 HT 35 4M 1370 0 83 0 09 2600 48 47 17 5 HT 40 4T 1350 1 66 0 96 0 25 4600 51 50 21 0 HT 40 4M 1370 2 00 0 25 4600 51 50 21 0 HT 45 4T 1370 2 02 1 17 0 37 6500 55 53 29 0 HT 45 4M 1400 2 76 0 37 6500 55 54 30 5 HT 50 4T 1380 2 92 1 69 0 55 8500 59 57 36 0 HT 50 4M 1350 4 40 0 55 8500 59 57 39 0 HT 56 4T 1410 3 10 1 79 0 75 9800 61 57 35 0 HT 56 4M 1410 5 05 0 75 9800 61 57 37 0 HT 56 ...

Страница 4: ...akustycznego dBA Przybliżona waga r min 220 277V 380 480V kW m3 h Inlet Outlet kg HT 25 4T 1740 0 65 0 38 0 09 1080 41 40 12 5 HT 25 4M 1740 0 65 0 10 1080 41 40 12 5 HT 31 4T 1716 0 65 0 38 0 09 1800 47 46 13 3 HT 31 4M 1716 0 83 0 09 1800 47 46 13 5 HT 35 4T 1632 0 65 0 38 0 09 2600 48 47 17 5 HT 35 4M 1632 0 83 0 09 2600 48 47 17 5 HT 40 4T 1680 1 66 0 96 0 25 4600 51 50 21 HT 40 4M 1680 2 00 0...

Страница 5: ...9 1800 47 46 13 3 HT ATEX 35 4T 1320 0 65 0 38 0 09 2600 48 47 17 5 HT ATEX 40 4T 1370 2 08 1 20 0 25 4600 51 50 21 0 HT ATEX 45 4T 1370 2 60 1 50 0 37 6500 55 53 29 0 HT ATEX 50 4T 1410 2 94 1 70 0 55 8500 59 57 36 0 HT ATEX 56 4T 1410 3 81 2 20 0 75 9800 61 57 35 0 HT ATEX 56 6T 910 2 42 1 40 0 25 6600 48 46 46 0 HT ATEX 63 4T 1410 5 20 3 00 1 10 14000 63 59 65 8 HT ATEX 63 6T 935 2 77 1 60 0 37...

Страница 6: ...wraz z opisem problemu w celu koordynacji jego zwrotu lub ewentualnej naprawy Przed uruchomieniem urządzenia należy zapewnić by zostały przeczytane instrukcje dotyczące bezpieczeństwa i instalacji zawarte w tym dokumencie oraz Generalnej Specyfikacji dla wentylatorów z certyfikatem ATEX dołączonej do dokumentacji produktu HT ATEX 4 Transport przechowywanie obsługa Zawsze montować urządzenie w prze...

Страница 7: ...to the power supply An external protective component must be connected a relay magneto thermal protection system or fuse in accordance with current regulations The equipment s earth connection must be connected If the motor speed control is used it must be guaranteed that the motor will operate correctly Start up After starting up the motor it is important to check that the motor is turning correc...

Страница 8: ...e problem in order to coordinate its return or possible repair Before starting up the equipment make sure you have read the safety and installation instructions set out in this document and the General Specifications for ATEX Fans attached to the product documentation HT ATEX 4 Transportation storage and handling Always hold the equipment at the points provided for this Fig 2 Do not lift it by the...

Страница 9: ...pply An external protective component must be connected a relay magneto thermal protection system or fuse in accordance with current regulations The equipment s earth connection must be connected If the motor speed control is used it must be guaranteed that the motor will operate correctly Start up After starting up the motor it is important to check that the motor is turning correctly without vib...

Страница 10: ...arcelona Spain Tel 34 93 8529111 Fax 34 93 8529042 comercial sodeca com www sodeca com 80 209 Chwaszczyno ul Polna 11A Zapraszamy pn pt 8 16 nkontakt tel tel kom 48 530 753 690 e mail sodeca scrol pl web www scrol pl SODECA W POLSCE 48 58 661 35 28 48 58 667 81 92 ...

Отзывы: