SWITCHING ON AND BATTERY CHARGING
Turn ON the Input switch on the back of the UPS
module. The display is now active.
Turn ON the battery switch on the back of the
battery xtension module.
The batteries are now charging, and will be fully
charged in approximately 8 hours.
PRESS - THE ON BUTTON UP TO BEEP
The LCD will display DIAGNOSTIC MODE, it will
be a few seconds before the UPS commences
normal operation.
The UPS can also be used with the batteries
not fully charged, though if a power cut occurs
backup time will be shorter.
The UPS may also be turned on with no mains
power, using only the batteries as a power
supply.
Be aware that if you do not press the on buttons
for 3 seconds, the LCD will be active but with
the UPS only on bypass mode and a yellow LED
flashing. No battery backup is availible.
STARTE UPS OG LADE BATTERIER
På baksiden av UPS-kabinettet er det en
inngangsbryter. Slå denne på, og skjermen blir
aktiv.
Slå på bryteren på baksiden av batterikabinettet.
Batteriene begynner nå å lades. La UPSen stå
på lading i minimum 8 timer for å lade batteriene
helt opp.
HOLD INNE PÅ-KNAPPEN TIL DU HØRER EN
KORT PIPELYD
LCD-skjermen vil vise “DIAGNOSTIC MODE”,
som tar noen sekunder før UPS er i normal drift.
UPSen kan brukes selv om batteriene ikke
er helt oppladet, men det vil medføre kortere
batteribackuptid ved strømbrudd.
UPSen kan også slås på uten strømtilførsel, den
bruker da de interne batteriene som strømkilde.
Dersom du ikke holder inne startknappen i
3 sekunder, kan det virke som om UPSen er
på. LCD-skjermen er aktiv, men UPSen er nå
i bypass - gul LED lyser, og du vil ikke ha aktiv
batteribackup.
MIMIC PANEL
A Display
B Red symbol - fault
C 2 colour LCD - Green is Normal, RED - is
overload
D Green LED lit - normal operation
E Power-on, Enter and Buzzer override button
F Scroll button - UP
G Scroll button - DOWN
H Off
button
I
Green LED: Lit - Mains healthy, Flashing -
Mains low but not lost
L 3 colour LEDs: Green - Battery power, Yellow
- Battery low, Red - replace battery
M Yellow LED: Lit - Bypass mode, Flashing -
Bypass voltage out of range
ENGLISH
NORWEGIAN
Den komplette manualen ligger på
vedlagte CD-plate.
The full operating manual is on the CD
ROM provided
Installasjon av UPS må tilfredsstille
nasjonale retningslinjer.
The UPS installation must comply with
relevant national regulations.
BATTERY MODE
The UPS automatically switches to battery
mode when mains power fails. In this mode the
Battery Mode LED indicator has a green light.
Low battery level is indicated with a Yellow light in
the battery symbol. Just before shutdown, when
battery charge runs out fully, low battery charge
is signalled via a rapid intermittent acoustic alarm.
The UPS automatically returns to normal
operating mode about two seconds after the
mains power is restored.
BATTERIDRIFT
UPSen vil automatisk bytte fra normal- til
batteridrift dersom strømtilførselen svikter. I
batteridrift vil LED-lampen i batterisymbolet lyse
grønt. Lavt batterinivå signaliseres ved et gult lys
i samme symbol. Like før UPSen slå seg helt av
fordi batteriet tømmes, vil du høre en lydalarm
hvert sekund.
UPSen vi automatisk returnere til normal drift
etter to sekunder når strømtilførselen er normal
igjen.
FORKLARING AV PANEL
A Skjerm
B Rødt symbol lyser betyr feil på UPS
C To farget LCD - Grønt betyr normalt, Rødt
betyr overlast
D Grønn LCD lyser betyr UPS i normal drift
E Knapp for å slå på UPS, er også knapp for
Enter eller slå av lyd
F Velge menyer på LCD - skroller oppover
G Velge menyer på LCD - skroller nedover
H AV-knapp
I
Grønn LED: Lyser betyr strømtilførsel OK,
blinker betyr lav men ikke borte
L 3-farget LED: Grønt - UPS i batteridrift, Gul -
lavt batterinivå, Rød - bytt batteri
M Gul LED: Lyser - UPS i bypass, Blinker - I
bypass, men dårlig strømkvalitet
110 DR
WNETR
T-XX
H
G
F
E
A
M
I
L
D
B
C
Battery
mode
Batteridrift
Connect the UPS to the mains, load and
battery. The electrical installation must be
performed by qualified technicians.
UPSen tilkobles nett, last og batteri. Dette
skal utføres av autorisert elektriker.