7. OPERATING MODES
7.4-2
7.4-1
Standby mode
1 sec
7.4. SETTING
MENU
Function
Description
Settings
Default settings
OPV
Output voltage selection
[208] = 208 V
[220] = 220 V
[230] = 230 V
[240] = 240 V
[230]
OPF
Output frequency selection
[050] = 50 Hz
[060] = 60 Hz
[050]
MODE
Work mode select
[UPS] = Normal
[ECO] = ECO mode
[CVF] = Converter mode
[UPS]
STY
Auto bypass enable disable
[000] = disable
[001] = enable
[000]