11
ENGLISH
ITYS
10-20 kVA - Ref.: IOMITYTWXX0C-GB 00
5. CONNECTIONS
The installation and the system must comply with national plant regulations. If a diff erential switch is installed on the mains power
switch (optional) it must be inserted upstream from the distribution panel.
CAUTION!
Use selective differentials. Any current dispersed by the loads will be summed to that of the UPS. The differential
protection must be regulated in cases of loads with high current dispersion.
NA
N
L
+
-
N
L
L3
N
L1
L2
L
N
L
N
JP1
JP2
MAINS
MAINS
AUX MAINS
AUX MAINS
OUTPUT
OUTPUT
UPS
Mains
Output
ø
UPS
ø
(mm²) (mm²)
≥ 10
10 kVA
≥ 10
≥ 21
20 kVA
≥ 21
5-2
5-1
5-4
ITYS B model
5-3
L
3
N
L
1
L
2
L
N
L
N
JP1
JP2
+
-
MAINS
MAINS
AUX MAINS
AUX MAINS
OUTPUT
OUTPUT
BATTERY
BATTERY
5-4
ITYS LB model
Содержание ITYS 10 kVA
Страница 21: ......