5.2.8.4
Local / Remote
The UPS can be connected to a remote equipment. By default the control panel
has the master function while the remote control has the slave function (all
controls are inhibited). Through this menu, controls can be sent from the remote
equipment.
CONFIGURATION:LOCAL-REMOTE
t
LOCAL
CONTROL
u
cancel validate
ESC
ENTER
5.2.9 JBUS link
Note: the JBUS link menu is only displayed if the setting is available on the UPS.
Configuration parameters are:
- the baudrate (1200 to 19200),
- the parity (none, even, odd),
- the slave number (001 to 255).
I PROGRAMMING 1
I
I baudrate: 19200
I
I Parity:
NONE
I
I Slave:
001
JBUS LINK
I
If a second JBUS link is available, the corresponding screen is automatically displayed
after completing the setting of the first JBUS link.