UPS/NTA GB/DELMP_EXPC1C3C6_B
14
2.6 OPERATING A SINGLE UPS
The « UPS COMMANDS » menu is designed for the operation of the UPS.
Note: controls are only displayed when available.
2.6.1 Starting up the UPS
Prior to any operation, please refer to the basic scheme of the system.
Conditions to be completed:
- The system is live,
- wait for the control panels to light up.
Comply with the following chronology procedure:
The UPS is started from the "UPS COMMANDS" menu and the "AUTOMATIC START UP"
sub-menu through an interactive procedure. Just follow the instructions displayed and
validate with the "ENTER" key.
Display for the automatic start up control:
UPS COMMANDS: AUTOMATIC START UP
CONFIRM THE START UP WITH UPS
SYSTEM OUTPUT SWITCHING ON
cancel validate
ESC
ENTER
2.6.2 Load transfer from inverter to mains
The load transfer is achieved from the "UPS COMMANDS" menu and the "LOAD TO
MAINS" submenu, which enables the seamless switching from the inverter source to the
non protected bypass source. Validate with the "ENTER" key.
Display for the LOAD TO MAINS control:
SUBSET COMMAND: LOAD TO MAINS
CONFIRM TRANSFER
TO AUTOMATIC BYPASS
cancel validate
'ESC' 'ENTER'