- 18 -
Example: If set the ratio to be 100,it means the primary current equals secondary currentx100
3.3.9 PT Setting
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer(PT) that wires to
the meter.
1
From the Set-up menu, use
and
buttons to select the
PT option. The screen will show the
voltage PT secondary voltage value. The
default value is 400V
2
Secondary PT setting
Press
to enter the PT
secondary voltage selection routine. The
range is from 100 to 500V
3
Set PT ratios value
Press
to enter the PT ratio
screen.
The range is from 0001 to 9999
For example, if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100