THREE PHASE DIN RAIL ENERGY METER 

COUNTIS M43 

MANUAL V1.0 

 

 

 

 

Содержание COUNTIS M43

Страница 1: ...SOCOMEC CHINA CO Ltd SOCOMEC CHINA CO Ltd SOCOMEC CHINA CO Ltd SOCOMEC CHINA CO Ltd http www socomec com THREE PHASE DIN RAIL ENERGY METER COUNTIS M43 MANUAL V1 0...

Страница 2: ...sages and chapters in this manual shall not be copied or reproduced or disseminated in any form Otherwise all consequences shall be borne by the violator Socomec reserves all legal rights Socomec rese...

Страница 3: ...cifications 2 1 Specifications 3 2 2 Accuracy 3 2 3 RS485 Communication 4 2 4 Environment 4 2 5 Dimendions 5 2 6 Wiring Diagram 5 Part 3 Operation Instructions 3 1 Display and Operation 6 3 1 1 Button...

Страница 4: ...3 4 Modbus Address 14 3 3 5 Baud Rate 15 3 3 6 Parity 15 3 3 7 Stop Bit 16 3 3 8 CT Setting 17 3 3 9 PT Setting 18 3 3 10 Pule Output 19 3 3 11 Pulse Constant 19 3 3 12 Pulse Duration 20 3 3 13 Set DI...

Страница 5: ...can be configured to work with a wide range of CTs giving the unit a wide range of operation Built in interfaces provides pulse and RS485 Modbus RTU outputs Configuration is password protected This u...

Страница 6: ...t An RS485 output allows remote monitoring from another display or a computer 1 3 Application COUNTIS M43 is a multi functional three phase energy meter designed for power system public facilities ind...

Страница 7: ...mary Current 1 9999A Second Current 1A or 5A Over current withstand 20 Imax for 0 01s Operational frequency Rated 50 60Hz Range 45 65 Hz Insulation capabilities AC voltage withstand 4KV 1min Impulse v...

Страница 8: ...l Modbus RTU Baud rate 2400 4800 9600 19200 38400bps Modbus Address 1 247 Bus load 64pcs Communication distance 1000m Parity EVEN ODD NONE Data bit 8 Stop bit 1 2 4 Environment Operating humidity 90 S...

Страница 9: ...ion against penetration of dust and water IP51 indoor Insulating encased meter of protective class II Altitude 2000m 2 5 Dimensions 2 6 Wiring Diagram 35mm Height 65 mm Width 72 mm Length 94 5 mm 3P4W...

Страница 10: ...n 3 Self checking finish 3 1 1 Button Definition 3 2 Measurement 3 2 1 Voltage Current Press button Selects V and A display screen In Set up Mode it is the Left or Back button Selects Hz and PF displa...

Страница 11: ...7 1 Phase to neutral voltages 3p4w 1 1 Phase to neutral voltages 3p3w 2 Current on each phase 3 Neutral current 4 Phase to neutral voltage THD 3p4w...

Страница 12: ...8 5 Current THD for each phase 3 2 2 Frequency Power Factor Demand Press button 1 Frequency and Power Factor total 2 Power Factor of each phase 3 Maximum Current Demand...

Страница 13: ...9 4 Maximum Power Demand 3 2 3 Power Press 1 Instantaneous Active Power in kW 2 Instantaneous Reactive Power in kVAr 3 Instantaneous Volt amps in KVA...

Страница 14: ...10 4 Total kW kVAr kVA 3 2 4 Energy Press button 1 Total active energy in kWh 2 Total reactive energy in kVArh 3 Imported active energy in kWh...

Страница 15: ...energy in kVArh 3 3 Setting by button To enter set up mode pressing the button for 3 seconds until the password screen appears Setting up is password protected so you must enter the correct password d...

Страница 16: ...m and top of list 2 Press to confirm your selection 3 If an item flashes then it can be adjusted by the and buttons If not there may be a further layer 4 Having selected an option from the current lay...

Страница 17: ...m left to right The procedure is as follows 1 The current digit to be set flashes and is set using the and 2 Press to confirm each digit setting The SET indicator appears after the last digit has been...

Страница 18: ...flash Press to exit the number setting routine and return to the Set up menu SET will be removed 3 3 4 Modbus Address The range is from 001 to 247 1 From the Set up menu use and buttons to select the...

Страница 19: ...ptions 2 4k 4 8k 9 6k 19 2k 38 4k 1 From the Set up menu use and buttons to select the Baud Rate option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to c...

Страница 20: ...select the Parity option 2 1 Press to enter the selection routine The current setting will flash 2 2 Use and buttons to choose Parity EVEN ODD NONE 3 3 7 Stop bit Option 1 or 2 1 From the Set up menu...

Страница 21: ...3 8 CT Setting The CT option sets the secondary current CT2 1A or 5A of the current transformer CT that wires to the meter 1 From the Set up menu use and buttons to select the CT option 2 Secondary CT...

Страница 22: ...Set up menu use and buttons to select the PT option The screen will show the voltage PT secondary voltage value The default value is 400V 2 Secondary PT setting Press to enter the PT secondary voltag...

Страница 23: ...kVArh 1 From the Set up menu use and buttons to select the Pulse output option 2 Press to enter the selection routine The unit symbol will flash Use and buttons to choose kWh or kVArh On completion of...

Страница 24: ...to enter the selection routine The current setting will flash Use and buttons to choose the Pulse Constant Press to confirm the setting and press to return to the main set up menu 3 3 12 Pulse Durati...

Страница 25: ...ting will flash Use and buttons to choose pulse width On Completion of the entry procedure press to confirm the setting and press to return to the main set up menu 3 3 13 Demand Integration Time This...

Страница 26: ...val will flash Use and buttons to select the time required ress to confirm the selection SET indicator will appear Press to exit the DIT selection routine and return to the menu 3 3 14 Set backlit las...

Страница 27: ...eing monitored 1 From the Set up menu use and buttons to select the System option The screen will show the currently selected power supply 2 Press to enter the selection routine The current selection...

Страница 28: ...reset the maximum demand value of current and power 1 From the Set up menu use and buttons to select the reset option 2 Press to enter the selection routine The MD will flash Press to confirm the set...

Страница 29: ...00 00 X 30003 Phase 2 line to neutral volts 4 Float V 00 02 X X 30005 Phase 3 line to neutral volts 4 Float V 00 04 X X 30007 Phase 1 current 4 Float A 00 06 30009 Phase 2 current 4 Float A 00 08 X 30...

Страница 30: ...e 00 22 X X 30037 Phase 1 phase angle 4 Float Degrees 00 24 X 30039 Phase 2 phase angle 4 Float Degrees 00 26 X X 30041 Phase 3 phase angle 4 Float Degrees 00 28 X X 30043 Average line to neutral volt...

Страница 31: ...87 Maximum total system power demand 2 4 Float W 00 56 30101 Total system VA demand 4 Float VA 00 64 30103 Maximum total system VA demand 4 Float VA 00 66 30105 Neutral current demand 4 Float Amps 00...

Страница 32: ...4 X 30249 Average line to neutral volts THD 4 Float 00 F8 X 30251 Average line current THD 4 Float 00 FA 30259 Phase 1 current demand 4 Float A 01 02 30261 Phase 2 current demand 4 Float A 01 04 X 302...

Страница 33: ...oat kWh 01 60 30355 L2 export kwh 4 Float kWh 01 62 X 30357 L3 export kWh 4 Float kWh 01 64 X 30359 L1 total kwh 3 4 Float kWh 01 66 30361 L2 total kWh 3 4 Float kWh 01 68 X 30363 L3 total kwh 3 4 Flo...

Страница 34: ...01 84 30391 resettable export active energy 4 Float kWh 01 86 30393 resettable import reactive energy 4 Float kVArh 01 88 30395 resettable export reactive energy 4 Float kVArh 01 8A Function code 10 t...

Страница 35: ...C Write pulse1 on period in milliseconds 60 100 or 200 default 100 Length 4 byte Data Format Float r w 40015 8 Password Lock 00 OE Write any value to password lock protected registers Read password lo...

Страница 36: ...rotocol default 1 Requires a restart to become effective Length 4 byte Data Format Float r w 40023 12 Pulse 1 Divisor 00 16 Write pulse divisor index n 1 to 6 1 0 01kwh imp 2 0 1kwh imp 3 1kwh imp 4 1...

Страница 37: ...CT Ratio primary current secondary current Length 4 byte Data Format Float Requires password see parameter 13 Non MID r w 40065 33 PT ratio 00 40 PT Ratio range 1 2000 PT ratio primary voltage second...

Страница 38: ...oat 461457 30729 Reset F0 10 00 00 reset the Maximum demand 00 03 reset the resettable energy Length 2 byte Data Format Hex wo 464513 32257 Serial number FC 00 Serial number Length 4 byte Data Format...