COUNTIS   E40/E41

GB

E

C

B

A

D

U

1

U

2

U

3

T1/T2 

*

*

 

COUNTIS E41

+ -

N

L2

L1

L3

N

L2

L1

L3

N

11

1

3

5

7

9

4 6 8 10 12 14 16 2

S1 S2

S1 S2

S1 S2

Web: www.socomec.com

Three phase kWh meter, 

measure via CT 50 to 6000 A

User instructions

Product presentation

A

LCD display.

B

Key to scroll readings.

C

"Prog" key to set up the CT ratio and the type of

network.

D

Reset to reset the partial counter.

E

Metrological LED (1 Wh = 10 impulses).

Meter setup 

The following settings have to be made before the

meter can be put to use : 

- CT ratio.

- Type of network (single or three-phase). 

- Type of three-phase installation (balanced or

unbalanced).

1. Press the Prog key during 3 sec. to enter the set-

up mode.

2. The CT ratio setting is displayed (100A). Press

the key "Read" repeatedly to scroll the possible

CT values (50, 100, 150, 200, 250, 300, 400, 600,

800… 6000A).

3. Press "Prog" to confirm and switch to the next

setting.

4. The type of network (1L+N, 2L, 3L, 3L+N) is

displayed. 

Press the key "Read" repeatedly to scroll the

possible values and select the type of network.

5. Press "Prog" to confirm and switch to the next

setting. 

6. On three-phase installations, the type of installa-

tion is displayed as "Balanced/Unbalanced" (Bl,

Unbl). 

Press the key "Read" to scroll the values and

select the type of installation. 

7. Press "Prog" to confirm. 
8. Press the Prog key during 3 sec. to exit the 

programming mode.

Display of readings

The various datas can be scrolled by pressing

the Key "Read".

The Default display will indicate power

consumption according to the current tariff.

COUNTIS E40

:

1

1

st

pressure : backlight switches ON.

Total active energy consumption (kWh).

2

2

nd

pressure : partial active energy

consumption (kWh).

3

3

rd

pressure : total reactive energy

consumption (kVAR).

4

4

th

pressure : partial reactive energy

consumption (kVAR).

5

5

th

pressure : instant power consumption

(kW).

COUNTIS E41

 :

The COUNTIS E41 provides detailed display of the

total/partial active energy consumptions accor-

ding to tariff (T1 or T2) and in total (T).

To reset the partial meter

- Press the scrolling key several times in order

to display partial energy.

- Press the reset button during 3 sec.

The partial meters (active and reactive energy)

will be set to zero.

ERROR message :

In case of bad wiring, an "ERROR" message

will be displayed.

- Check for each phase that current (I1, I2, I3)

and voltage (L1, L2, L3) are measured on the

right phase.

- Check the correct wiring of the product (L/N).

Note :

The information 

on the display indicates

that the corresponding phase (1, 2,3) is under

voltage.

Technical specifications

Metrological characteristics

- Accuracy class B (1%) according to EN50470-3

- Metrological LED : 

1 pulse = 0.1Wh current transformer ratio

e.g. in a installation with a 100/5A C.T.,

1 pulse = 0.1Wh /20 pulses = 2Wh

- Starting current : 10 mA

- Basic current : 5 A

- Max current : 6 A

Technical characteristics

Note:

in a unbalanced network, please connect 1 C.T.

for each phase.

if the installation settings is related to a

"balanced network", 1 C.T. on the phase 1 has to be

connected

- Consumption: < 0,6 W et 2,8 VA max per phase

- Supply : 230/400 V

+/- 15%

- Frequency : 50/60 Hz +/- 2 Hz

- Savings of measures are made regularly and in

case of power failure in EEPROM

- Characteristic of tariff input

COUNTIS E41

 : 

tariff 1 = 0 V,  tariff 2 = 230 V

+/- 15%

- Impulse output characteristics : 

 1 pulse : 100 Wh 

 Pulse duration : 100 ms 

 External supply :20 ... 30 V 

Mechanical characteristics

- Modular casing 4 M (72 mm)

- Protection degree (casing) : IP20

- Protection degree noze : IP50/IK03

- Insulation class : II

Environment

- Storage temperature : -25 °C to +70 °C

- Working temperature : -10 °C to +55 °C

- Connection capacity :

 flexible : 1 à 6 mm

2

 rigid

: 1,5 à 10 mm

2

Operating principle

This kilowatt hour meter measures the active and reactive electrical energy used in an electrical

installation.

This device has a digital LCD to display energy used and power.

This device has a total counter and a partial resettable counter.

In case of two tariff levels, the 

COUNTIS E41

 will count separetely the energy used in tariff 1 and in tariff 2.