Three-phase Digital Energy meters - Direct connection 63A M-Bus
This equipment must be mounted only by professionals. The manufacturer cannot be held liable for any
failure to follow the instructions given in this document and in document 542104 which can be downloa-
ded from the website: www.socomec.com.
Risk of electrocution, burns or explosion
• this device must only be installed and maintained by qualified
and duly authorised personnel
• always use a suitable voltage tester to ensure there is no
voltage supplied to the device
• put all mechanisms, door and covers back in place before
energising the device
• always supply the device with the correct rated voltage
Failure to take these precautions could cause serious injuries.
Risk of damaging device
Chek the following :
• the frequency of the distribution
system IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• the maximum voltage at the
voltage input terminals is 276 VAC
phase / neutral
• a maximum current of 63 A
FR
Compteur d’énergie triphasé - Direct 63A M-Bus
Le montage de ces matériels ne peut être effectué que par des professionnels. Le non respect des
indications de la présente notice ainsi que la notice générale 542104 téléchargeable sur le site : www.
socomec.com ne saurait engager la responsabilité du constructeur.
Risque d’électrocution, de brûlures ou d’explosion
• l’installation et l’entretien de cet appareil ne doivent être
effectués que par du personnel qualifié et habilité
• utilisez toujours un vérificateur d’absence de tension
approprié pour confirmer l’absence de tension
• replacez tous les dispositifs, les portes et les couvercles
avant de mettre cet appareil sous tension
• utilisez toujours la tension assignée appropriée pour
alimenter cet appareil.
Si ces précautions n’étaient pas respectées, cela pourrait entraî-
ner des blessures graves.
Risque de détérioration de
l’appareil
Veillez à respecter :
• la fréquence du réseau
CEI: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• une tension maximum aux bornes
des entrées tension de 276 VAC
phase / neutre
• un courant maximum de 63 A
DE
Wirkenergiezähler für Drei-phasige Netze - Direkt 63A M-Bus
Die Montage muss von einem Fachmann vorgenommen werden. Werden die Anweisungen der vor-
liegenden Anweisung sowie die allgemeine Bedienungsanleitung 542104, die auf der Webseite: www.
socomec.com heruntergeladen werden kann, nicht beachtet, entfällt die Haftung des Herstellers.
Gefahr von Stromschlägen, Verbrennungen oder
Explosionen
• Dieses Gerät darf nur von einer entsprechend qualifizierten und
befugten Personen installiert und gewartet werden.
• Stellen Sie mit Hilfe eines geeigneten Spannungs
anzeigegeräts sicher, dass keine Spannung anliegt.
• Alle Vorrichtungen, Türen und Deckel vor dem erneuten
Einschalten des Gerätes wieder anbriegen.
• Nur die vorgegebene Spannung zur Versorgung des Gerätes
verwenden.
Eine Nichteinhaltung dieser Vorsichtsmaßnahmen kann zu
schweren Verletzungen führen
Gefahr einer Beschädigung
des Gerätes
Bitte beachten Sie:
• Die Netzfrequenz
IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• Eine maximale Spannung an den
Spannungseingangsklemmen von
276 V Phase / Neutral
• Einen maximalen Strom von 63 A
IT
Contatore di energia trifase - Diretto 63A M-Bus
Questi prodotti devono essere montati esclusivamente da professionisti;Il mancato rispetto delle indica-
zioni contenute nel presente manuale o nel file 542104 scaricabile sul sito www.socomec.com, solleva il
costruttore da ogni responsabilità.
Rischi di folgorazione, ustioni o esplosione.
• L'installazione e la manutenzione ordinaria di questo
apparecchio devono essere effettuate esclusivamente da
personale qualificato e abilitato.
• Utilizzare sempre un opportuno dispositivo di rilevamento di
tensione per confermare l’assenza di tensione.
• Rimontare tutti i dispositivi, le portelle e i coperchi prima di
mettere l’apparecchio sotto tensione.
• utilizzare sempre la tensione opportuna per alimentare
questo apparecchio.
Il mancato rispetto di queste precauzioni potrebbe comportare
gravi lesioni.
Rischi di deterioramento
dell’apparecchio.
Attenzione rispettare:
• La frequenza di rete
IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• Una tensione massima ai morsetti
degli ingressi di tensione da
276 VAC fase / neutro.
• Una corrente massima di 63 A.
ES
Contadores de energía trifásicas - Directo 63A M-Bus
El montaje de esto materiales sólo puede ser efectuado por profesionales. Si no se cumplen la indica-
ciones mencionadas en el presente manual o el manual de uso 542104 descargable en www.socomec.
com, se excluye cualquier responsabilidad del fabricante.
Riesgo de electrocución, de quemaduras o de
explosión
• la instalación y el mantenimiento de este equipo deberan
correr a cargo de personal cualificado y homologado
• utilice siempre un comprobador de ausencia de tensión
adecuado para confirmar la ausencia de tensión
• volver a colocar todos los dispositivos, tapas y puertas antes
de poner el aparato en tensión
• utilice siempre la tensión asignada adecuada para alimentar
el aparato
Si no se adoptan estas precauciones, existe riesgo de sufrir
lesiones graves.
Riesgo de deterioro del
aparato
Si requiere respetar:
• la frecuencia de la red
IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• una tensión maxima en los bornes
de las entradas de tensión de 276
VAC fase / neutro
• la intensidad máxima de 63 A
PT
Contador de energia trifásica - Directa 63A M-Bus
A montagem destes materiais só pode ser realizada por profissionais. O não cumprimento das indica-
ções deste manualassim como do manual de instrução geral 542104 disponível no site: www.socomec.
com, não poderá imputar a responsabilidade do construtor.
Riscos de electrocussão, de queimaduras ou de explosão
• a instalação e a manutenção deste aparelho só devem ser
efectuadas por pessoal qualificado e com habilitações para tal
• utilize sempre um verificador de ausência de tensão apropriado,
para confirmar a ausência de tensão
• colocar no sítio todos os dispositivos, as portas e as tampas
antes de restabelecer a tensão no aparelho
• utilizar sempre a tensão de referência apropriada para alimentar
o aparelho
Se estas precauções não forem respeitadas, poderão ocorrer
ferimentos graves.
Riscos de deterioração
do aparelho
Respeitar:
• a frequência da rede
IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• uma tensão máxima nos
terminais das entradas tensão
de 276 VAC fase / neutro
• uma corrente máxima de
63 A
NL
Driefasig energieteller - Direct 63A M-Bus
Het monteren van dit material mag enkel gebeuren door professionelen. Bij het niet respecteren van de
aanwijzingen in dit instructive-bericht, alsook de algemene instructies 542104, te downlaoden op de
website www.socomec.com , vervalt de verantwoordelijkheid van de fabricant.
Risico van elektrocutie, brandwonden of explosie
• de installatie en het onderhoud van dit apparaat mogen alleen
worden uitgevoerd door gekwalificeerd en bekwaam personeel
• gebruik altijd een goede spanningstester om te controleren of er
geen spanning is
• alle onderdelen, deuren en deksels terugplaatsen alvorens het
toestel onder spanning te zetten
• gebruik altijd de juiste nominale spanning om dit toestel te voeden
Indien deze voorschriften niet in acht worden genomen, kan dit
ernstige verwondingen tot gevolg hebben.
Risico van beschadiging
van het toestel
Gelieve de volgende
elementen in acht te nemen:
• de spanning van de
hulpvoeding
IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• een maximumspanning op
de ingangsaansluitingen,
spanning van 276 VAC fase /
neutraal
• een maximale stroom van 63 A
TR
Üç fazlı Dijital Enerji analizörleri – 63A M-Bus Bağlantısı
Bu ekipmanın montajı sadece yetkin kişiler tarafından yapılmalıdır. Bu ve 542104 numaralı dokümandaki
montaj talimatlarına www.socomec.com adresinden ulaşılabilir. Bu talimatlar sırasında ortaya çıkacak
arızalarda üretici firma sorumlu tutulamaz.
Elektrik çarpması, yanma veya patlama riski
• Bu cihazın kurulumu ve bakımı sadece bu işe yetkin ve yeterli
bilgiye sahip kişiler tarafından yapılmalıdır.
• Cihazın besleme gerilimi olup olmadığından emin olmak için her
zaman uygun bir gerilim test cihazı kullanın.
• Cihaza besleme gerilimi uygulamadan önce tüm parçaları ve
kapakları yerine monte edin.
• Cihazı daima nominal çalışma gerilimi ile besleyin.
Bu talimatlara uyulmaması ciddi yaralanmalara neden olabilir.
Arıza riski
Kontrol edin:
• Dağıtım sisteminin frekansı
IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• Giriş gerilimi max. 276 VAC
faz / nötr
• Max. akım 63 A
PL
Trójfazowy licznik energii czynnej - pomiar bezpośredni do 63 A, komu-
nikacja M-Bus
Niniejsze urządzenie powinno być instalowane wyłącznie przez osoby wykwalifikowane. Producent nie
ponosi żadnej odpowiedzialności za jakiekolwiek uszkodzenia wynikające z nieprzestrzegania instrukcji
zawartych w niniejszym dokumencie oraz w dokumencie nr 542104 który można pobrać ze strony inter-
netowej: www.socomec.com
Niebezpieczeństwo porażenia prądem, oparzenia lub
wybuchu
• urządzenie powinno być instalowane i konserwowane wyłącznie
przez osoby wykwalifikowane i uprawnione
• w celu sprawdzenia, czy do urządzenia jest podłączone napięcie,
korzystać zawsze z odpowiedniego próbnika napięcia
• przed podłączeniem urządzenia do zasilania, zamocować
wszystkie mechanizmy, drzwiczki i pokrywy na swoim miejscu
• zawsze zasilać urządzenie odpowiednim napięciem
znamionowym
Nieprzestrzeganie niniejszych środków ostrożności może być
przyczyną poważnych obrażeń.
Niebezpieczeństwo
uszkodzenia urządzenia:
Sprawdzić:
• częstotliwość sieci zasilającej
IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• czy maksymalne napięcie
na zaciskach wejściowych
wynosi 276 VAC faza /
neutralny
• maksymalny prąd 63 A
ZH
三相数字式电能表 — 直连 63A M-Bus
该装置必须由专业人员进行安装。如不遵守本文档及 542104 号文档中的说明使用所产生的任何后果,制
造商不承担责任;542104 号文档可在该网站下载:www.socomec.com
.
有触电致死,燃烧以及爆炸的危险
• 该装置必须由具备专业资质的人员进行安装与检修
• 始终使用合适的电压检测装置来确定无电压
• 在给该装置通电之前,将所有的机械装置、门、封盖都归位
• 始终供给装置正确的额定电压
不遵守上述规范将会导致严重伤害。
导致装置损坏的风险
请检查以下几项:
• 电网频率 IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
• 电压输入端的最大电压为 276
V 相/中性
• 最大电流 63 A
Technical characteristics
Data in compliance with EN 504701, EN 504703
MID
Device code
and certification
data indications
General
Housing
4 modules DIN 43880
Mounting
DIN rail EN 60715
Depth
72 mm
Operating features
Connectivity
4 wires 230/400V
Storage of energy values and configuration
yes EEPROM
Display tariffs identifier
T1 and T2
Supply
Operating voltage range
92 ... 276 VAC
Operating frequency range
45 ... 65 Hz
Maximum power dissipation (voltage circuit)
≤2 (0.6) VA (W)
Overload capability
Voltage Un continuous
480 VAC phase to phase
Voltage Un momentary (1 s)
800 V phase to phase
Current Imax continuous
63 A
Current Imax momentary (1 s)
1890 A
Display
Display type
9 (2 decimal) digits
Active energy: 1 display, 9digit
0.01 > 9999999.99 kWh
Display period refresh
1 s
Measuring accuracy
Active energy and power
class B class EN 504703
Measuring input
Type of connection
400 V phase to phase
Certified voltage Un
230 VAC
Current Iref
5 A
Current Imin
0.25 A
Operating range current (Ist ... Imax)
0.015 ... 63 A
Certified frequency fn
IEC: 50/60 Hz ± 1 Hz
MID: 50 Hz ± 1 Hz
Starting current for energy measurement (Ist)
15 mA
Optical interfaces
Meter constant
1 Wh/imp
Safety
Indoor meter
yes
Degree of pollution
2
Operational voltage
300 VAC
AC voltage test (EN 504703, 7.2)
4 kV
Impulse voltage test
6 kV
Protection class (EN 50470)
class II
Housing material flame resistance
class V0
Embedded communication
MBus
2 wires up to 9600 bps
Isolation class
SELV circuit
Connection terminals
Terminal capacity current paths
flexible or rigid: 1.5 to 35 mm
2
Terminal capacity COM and tariff
flexible 1.5 to 2.5 / rigid 1 to 4 mm
2
Environmental conditions
Mechanical environment
M1
Electromagnetic environment
E2
Operating temperature
25 ... +55 °C
Limit temperature of transportation and storage
25 ... +70 °C
Relative humidity (not condensation)
≤80 %
Vibrations
±0.075 mm
Degree protection
IP51(*)/IP20
(*) For the installation in a cabinet at least with IP51 protection.
COUNTIS E25 : ref. 4850 3037
COUNTIS E26 (MID) : ref. 4850 3038
COUNTIS
E25/E26
Three-phase Digital Energy meters
Direct connection 63A M-Bus
542 113 C
- 02/16
QUICK
START
EN
FR
DE
IT
ES
PT
NL
TR
PL
ZH
www.socomec.com
Certificate of conformity
with MID Directive,
User Manual:
http://www.socomec.com/en/
countise2x