COUNTIS E03
COUNTIS E04 - MID
Single-phase energy meter
Direct - 40 A Modbus
COUNTIS
E03
/
E04
INSTRUCTION MANUAL
EN
www.socomec.com/en/countis-e0x
Страница 1: ...COUNTIS E03 COUNTIS E04 MID Single phase energy meter Direct 40 A Modbus COUNTIS E03 E04 INSTRUCTION MANUAL EN www socomec com en countis e0x...
Страница 2: ...0 6 2 Connection to the electrical network and to the loads 10 7 MID COMPLIANCE 11 8 COMMUNICATION 12 8 1 General information 12 8 2 RS485 rules 12 8 3 Communication structure 13 8 4 Communication tab...
Страница 3: ...3 EN COUNTIS E03 E04 545865A SOCOMEC 1 DOCUMENTATION All documentation on the COUNTIS E03 E04 is available online at www socomec com en countis e0x...
Страница 4: ...designed to be repaired by the user For any questions related to the disposal of the device please contact SOCOMEC Failure to comply with the instructions of the device and this safety information can...
Страница 5: ...of these instructions thoroughly before commissioning Check the following points as soon as you receive the package containing the unit The packaging is in good condition The unit has not been damaged...
Страница 6: ...communication bus 4 2 Functions Measures and displays total and partial energy Dual tariff management T1 T2 Electrical parameter measurements I U V f Power power factor RS 485 modbus communication MID...
Страница 7: ...Main zone in the event of Code XX metrological setting corrupt return to manufacturer 5 Value of the partial meter Flashing meter stopped 6 Active communication 7 Inductive value 8 Imported or exporte...
Страница 8: ...Total active and reactive energy Ea Er kWh kvarh Total apparent energy Eap kVAh Total reactive inductive and capacitive energy Er kvarh Total active and reactive energy for each tariff T1 T2 Ea Er kWh...
Страница 9: ...o the safety instructions section 2 Hazards and warnings page 4 Keep away from electromagnetic interference generator systems Avoid vibrations with accelerations greater than 1 g for frequencies lower...
Страница 10: ...Connection to the electrical network and to the loads The COUNTIS E03 E04 are intended for single phase networks with neutral Modbus 1 2 3 NC not connected May be used for shielding continuity Pulse...
Страница 11: ...2 Connection to the electrical network and to the loads page 10 Fitting terminal covers After connecting the device ensure that the terminal covers are fitted properly and secured by the plastic seals...
Страница 12: ...N 2 NC N n NC N 1 NC NC NC N n Programmable machines Programmable machines Other systems Other systems Repeater 8 2 RS485 rules A LIYCY shielded twisted pair must be used We recommend using a shielded...
Страница 13: ...ly with the modbus protocol the inter character time must be 3 silences This means the time for 3 characters to be emitted so that the message is processed by the COUNTIS E03 E04 In order to use the i...
Страница 14: ...within a menu Realtime Go to SETUP menu Menu page SETUP 3 sec Change a value digit SETUP pages real time Confirm a value digit SETUP pages 3 sec Exit SETUP menu SAVE screen from the SETUP menu 3 sec S...
Страница 15: ...ed view of menu SETUP 3s Communication address 1 2 5 246 247 Communication speed 2400 4800 9600 19200 38400 Communication parity n no o odd E even Reset energy Ea partial Ea partial Eap partial Er par...
Страница 16: ...munication address In SETUP mode see page 14 go to the Addr communication address screen Example changing the communication address to 247 3 sec 3 sec x2 3 sec x4 3 sec x2 3 sec x1 Communication speed...
Страница 17: ...ported reactive energy ______________ Tariff 2 Imported active energy ______________ Tariff 2 Imported reactive energy ______________ Total imported active energy ______________ Total exported active...
Страница 18: ...Imported active energy Tariff 2 Imported reactive energy Total imported active energy description in chapter 10 1 1 Total exported active energy Total imported reactive energy description in chapter...
Страница 19: ...EC 10 1 1 Detailed view of the partial energy meter Total imported active energy Total imported reactive energy 10 1 2 Starting up the partial energy meter 3 sec 3 sec 3 sec 10 1 3 Stopping the partia...
Страница 20: ...20 EN COUNTIS E03 E04 545865A SOCOMEC 10 1 4 Resetting the partial energy meter to zero 3 sec x1 3 sec...
Страница 21: ...there are connection or malfunction errors 11 1 Malfunction When messages with the code xx are displayed the meter has malfunctioned and must be replaced 12 ASSISTANCE Causes Solutions Device not wor...
Страница 22: ...ut consumption 0 5 VA Start up current Ist 20 A Minimum current Imin 0 25 A Transition current Itr 0 5 A Reference current Iref 5 A Permanent overload lmax 40 A Intermittent overload 30 Imax for 1 2 c...
Страница 23: ...ctive power 1 display 4 digit 00 00 99 99 kW Realtime reactive power 1 display 4 digit 00 00 99 99 kvar Realtime voltage 1 display 4 digit 000 0 999 9 V Realtime current 1 display 4 digit 00 00 99 99...
Страница 24: ...W x H x D mm Modular width of 1 module DIN 43880 18 x 90 x 70 Installation On DIN rail EN 60715 Connection capacity tightening torque See chapter 6 Connection page 10 Protection index Front IP51 casin...
Страница 25: ...gical firmware t 1 Tariff 1 t 1 Tariff 2 Set up Set up menu Addr Slave address bAu Communication speed in bauds bits per second Prty Communication frame parity n No parity o Off parity E Even parity R...
Страница 26: ...Non contractual document 2016 Socomec SAS All rights reserved 545865A CORPORATE HQ CONTACT SOCOMEC SAS 1 4 RUE DE WESTHOUSE 67235 BENFELD FRANCE www socomec com...