ASYS
16 A Transfer System
ENGLISH
IOMASY160810-GB_00
11
T
ECHNICAl
D
ATA
7.
I
NpUT
/ O
UTpUT
fEATURES
7. 1.
ASYS 16A-120
ASYS 16A-230
INPUT
Nominal voltages
120V
220/230/240V selectable
Voltage acceptance window
N/- 12%* to +/- 20% adjustable**
Working range voltage
80 ~ 145Vac
160 ~ 290Vac
Nominal frequency
50/60 Hz auto sensing
acce/- 15%
Current
16 Amps
OUTPUT
Voltage range
same as input
Nominal frequency
same as input
Current
16 Amps
Typical Transfer time
6ms
Maximum Transfer time
<= 15ms
* = default
** = on demand
C
ONNECTION
7. 2.
ASYS 16A-120
ASYS 16A-230
INLET
Power cord
AWG12X3C/20A
2 x IEC 320-C20
OUTLET
4 x NEMA 5-20R
1 x IEC 320-C19
2 x 3 x IEC 320-C13