RS232 <=> RTC<=> RS485
Modem
8
SOCOMEC - Réf. : 874 669 A GB
SPECIFICATIONS
Type tests and environmental conditions
ENVIRONMENTAL
Phenomena
Test
Description
Test levels
Temperature
Operating
-25 to +70 °C
Storage & Transport
-40 to +70 °C
Humidity
Operating
5 to 95 % relative humidity non condensing
Storage & Transport
5 to 95 % relative humidity non condensing
Altitude
Operating
2 000 m / 70 kPa
Reliability prediction (MTBF)
MIL-HDBK- 217F Operating
Service life
Operating
10 years
Vibration
IEC 60068-2-6 Operating
7.5 mm, 5 - 8 Hz
2 g, 8 - 500 Hz
Shock
IEC 60068-2-27 Operating
15 g, 11 ms
PACKAGING
Phenomena
Test
Description
Test levels
Enclosure
UL 94
PC / ABS
Flammability class V-1
Dimension W x H x D
55 x 100 x 132 mm
Weight
0.36 kg
Degree of protection
IEC 529
Enclosure
IP 20
Cooling
Convection
Mounting
Horizontal on 35 mm DIN-rail