6
COUNTIS E13/E14
- Ref.: 542 101 A
5.4. Connections
5.4.1. 2-wire connection - single-phase load monitoring
L1
L1
N
230 VAC fn = 50 Hz
L1
L’
N
80A
6
1
5
4
3
2
230 VAC
120Ω -
+
NC
T1/2
COM RS485
Modbus/Jbus
MODBUS
1:
Activation of 120 ohm terminating resistors by
connecting terminals 1 and 2.
2:
-
3:
+
4:
NC (not connected).
Tariff
5-6:
Change of tariff only for COUNTIS E14:
0 VAC -> Tariff 1
230 VAC -> Tariff 2
(change of tariff via MODBUS for COUNTIS E13).
Mains
L1
:
Phase input.
L1
:
Phase output.
N:
Neutral connection.
5.5. Sealable covers
COUNTIS E14 MID
Label scaled
between front and
rear faces
Plastic seal
Terminal covers